6 | Operation
INFICON
70 / 146
UL6000-Fab-Operating-instructions-iina75en1-04-(2109)
A currently displayed leak is hidden through ZERO.
By using the function ZERO not only is the background signal hidden, but also the
representation of a current leak.
► If you want to prevent this, select the function ZERO only if not measuring a leak at
the same time.
Activate or deactivate
ZERO
ZERO is activated by factory settings.
ü
Supervisor rights
1
> Setup > Measurement > ZERO and filter
2
If necessary change "ZERO mode". The factory setting is “I•ZERO 2.0”.
ð
You can choose between "I•ZERO 2.0", "ZERO" and "Switched off".
ð
If you select "OFF”, the ZERO button does not work.
3
Save
.
ð
If ZERO is activated, start the function by pressing the ZERO button. See also
26]".
How do I switch the
ZERO function ON?
Briefly press the ZERO button on the control panel or the touchscreen
.
How do I switch the
ZERO function OFF?
Press the ZERO button on the control panel for more than 2 seconds or on the
touchscreen
.
“Vacuum" operation
mode, effect of ZERO
setting
If you use the "I•ZERO 2.0" setting, after pressing the ZERO button the displayed
background signal is faded out depending on the current drift. Typically, the display
limit falls in several steps. The size of the current display limit is a dimension with
which leakages can currently be measured. When measuring, the current display limit
should be at least one decade below the expected measured value.
If you use the "ZERO" setting, the currently displayed leak rate value is set to the
lower display limit after pressing the ZERO button.
"Vacuum" operation
mode, “HYDRO•S“
switched on, setting
"I•ZERO 2.0" or
“ZERO“
When you press the ZERO button, the current leak rate value is set to the lower
display limit.
Note: The ZERO button should not be pressed when there is a rapidly falling
background, otherwise, when compared to the background change, small leak rate
signals may be incorrectly hidden.
"Sniffing" operation
mode, setting "I•ZERO
2.0" or “ZERO“
When you press the ZERO button, the current leak rate value is set to the lower
display limit.
Содержание 550-520
Страница 2: ...INFICON GmbH Bonner Strasse 498 50968 Cologne Germany ...
Страница 119: ...INFICON Decommissioning 9 UL6000 Fab Operating instructions iina75en1 04 2109 119 146 ...
Страница 139: ...INFICON Appendix 11 UL6000 Fab Operating instructions iina75en1 04 2109 139 146 11 2 CE Declaration of Conformity ...
Страница 140: ...11 Appendix INFICON 140 146 UL6000 Fab Operating instructions iina75en1 04 2109 11 3 RoHS ...
Страница 143: ...INFICON Index UL6000 Fab Operating instructions iina75en1 04 2109 143 146 Z ZERO 77 Button 26 Factory setting 70 ...
Страница 144: ...Index INFICON 144 146 UL6000 Fab Operating instructions iina75en1 04 2109 ...
Страница 145: ......
Страница 146: ......