background image

C

N

L'

L

N

L'

L

N

L'

L

70

98

21

44

98

3.Puttingintooperation/Settings

Factory settings

The PD4-M-1C-GH is preset with time setting 5 min. and twilight switch 

1000 Lux. 

Attention:

Changes to the settings can only be made by remote control IR-PD4-GH.

Installation and Operating Instruction for 

B.E.G.

-Occupancy detectors PD4-M-1C/-S-GH-SM

2a.InstallationoftheLUXOMAT

®

PD4-M-1C-GH-SM

4.PD4-M-1C-GH:Settingscarriedoutusingremote

control(optional)

Remote control LUXOMAT

®

 IR-PD4-GH

1. Check Battery:

 

Open battery compartment by pressing the plastic 

springs together and removing the battery-holder.

1.Mountingpreparations

Work on the 230 V mains supply 

may only be carried out by qualified 

professionals or by instructed persons 

under the direction and supervision of 

qualified skilled electrical personnel in 

accordance with electrical regulations.

Disconnect supply before installing!

The device is not suited for safe dis-

connection of the mains supply. 

When in Master/Slave mode of 

operation, the Master-appliance must 

always be installed at the location 

where there is least daylight.

Option:

Wallbracketforremotecontrol

IR-PD4-GH

2c.Selftestcycle

IR-PD4-GH

IR-PD-Mini

B.E.G.

LUXOMAT

®

PD4-M-1C/-S-GH-SM

The detector must be in stalled on a solid and  

level surface. The circular cover ring must be removed 

prior to assembly. To do this, twist the lens (C) anti-

clockwise through approximately 5° and lift off. 

Having connected up the wires in accordance with 

regulations, secure the detector with 2 screws.  

After installation replace the lens and lock (turn clock-

wise). Mains to be connected.

ATTENTION:

 Install the unit in such a manner that 

both markings on the housing are positioned in the 

longitudinal axis of the area to be monitored (e.g. 

high-bay corridors)

5.PD4-M-1C-GH-SM-Dimensions

2b.Rangeindependencefromthemountingheight

Mounting 

height

Range (circular detection) T=17°C

Walking across

  2.00 m

r =   7.50 m

Ø

 = 15.00 m

  2.50 m

r =   9.00 m

Ø

 = 18.00 m

  3.00 m

r = 11.00 m

Ø

 = 22.00 m

  3.50 m

r = 13.00 m

Ø

 = 26.00 m

  4.00 m

r = 15.00 m

Ø

 = 30.00 m

  4.50 m

r = 17.00 m

Ø

 = 34.00 m

  5.00 m

r = 18.50 m

Ø

 = 37.00 m

  6.00 m

r = 18.50 m

Ø

 = 37.00 m

  7.00 m

r = 18.50 m

Ø

 = 37.00 m

  8.00 m

r = 22.00 m

Ø

 = 44.00 m

  9.00 m

r = 22.00 m

Ø

 = 44.00 m

10.00 m

r = 22.00 m

Ø

 = 44.00 m

r=radius  /  Ø=diameter

close

open

GB

The product enters an initial 60-second 

self-test cycle, when the supply is first 

connected. The occupancy detector is 

ready for operation.

During the selftest cycle, the following 

settings can be made:

Light stop active: 

(A)

Light off active: 

(B)

(see point 7)

Unlocking device

or

or

or

or

Lock device

Settings for relay 

Channel 1: 

��

�������

���

��

���

��

���

Settings for master with remote control

Reset when 

open: 

Deletes 

all values set 

with the remote 

control, loads 

the default 

settings 

HA

OFF

Adjust the target value 

for brightness

+

+

Target value for brightness
Automatic reading in of the current light value 

as a new target light value
Sun button - specified twilight value 

Daytime operation

Lag time 
Pulse function, fully automatic mode active
Switch between fully automatic/semi-automatic mode 

Semi-automatic mode active: Red + green LEDs flash 3x every 

5 seconds

Adjust the target value for brightness  

to reach the calculated target value, increase the light value by 

approx. 50 lux each time the button is pressed

Test mode when closed:  

exited automatically after 3 minutes

Test mode when open:  

not exited automatically

To deactivate: 

press reset

Reset when closed 

The lighting relay is switched off, i.e. opened and the lag times 

are reset.

Light on/off when closed

(A) 

The light remains on/off until movements are detected in 

the detection area. After the last detected movement, the light 

remains off for the duration of the set lag time. 

(B) 

If the “Light 

stop” function was activated in the selftest cycle, the light is 

switched off for 5 seconds (red and green LEDs flash). The device 

then returns automatically to the selected operating mode (fully or 

semi-automatic mode).

��

���

����

���

Explanation of button functions

��

���

��

���

HA

ON

HA

OFF

9s

2s

LED ON

LED OFF

Pulse spacing PD-Slave

2 or 9 seconds can be set for the pause between  

2 pulses sent to the master.  The setting can be made 

with activated ( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be 

set.

Отзывы: