background image

Technické parametry / Technical parameters 

Všeobecné instrukce / General instructions 

barevný TFT LCD
3:4
52.5 x 70 mm
aktivní
rezistivní 4 vodičová
3.5”
240 x 320
16.7M
27V DC/ 150mA
svorkovnice
max. 2.5mm

2

/1.5mm

2

 s dutinkou

0 .. +55°C
- 20 .. +70°C
IP20
III.
2
libovolná
do instalační krabice
94 x 94 x 30 mm

Displej
Typ:
Poměr stran:
Viditelná plocha:
Podsvícení:
Dotyková plocha:
Úhlopříčka:
Počet bodů:
Hloubka barev:
Napájecí napětí/jm. proud:
Připojení:
Průřez připojovacích vodičů:
Pracovní teplota:
Skladovací teplota:
Krytí:
Kategorie přepětí:
Stupeň znečištění:
Pracovní poloha:
Instalace:
Rozměry:

Display
Typ:
Aspect ratio:
Visible area:
Back-light:
Touch-screen area:
Diagonal:
Resolution:
Colour intensity:
Supply voltage/rated current:
Connection:
Connecting conductors profi le:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Dimensions:

full-colour TFT LCD
3:4
52.5 x 70 mm
active
resistive 4 conductor
3.5”
240 x 320
16.7 M
27V DC/ 150mA
terminal box
max. 2.5mm

2

/1.5mm

2

 with  contact tube 

0 .. +55°C
- 20 .. +70°C
IP20
III.
2
any
into installation box
94 x 94 x 30 mm

ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | 
e-mail: [email protected]
TECHNICAL SUPPORT | E-mail: [email protected] | Mobil: +420 778 427 366 | 
Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com

ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Česká republika | 
e-mail: [email protected]
TECHNICKÁ PODPORA | E-mail: [email protected]
Mobil: +420 778 520 926 | Tel.: +420 573 514 275, +420 | 573 514 211 | 
Fax: +420 573 514 227 | www.inels.cz

CONNECTING TO THE SYSTEM
Wires of data BUS of iNELS system must be connected to a terminal block 
BUS+ and BUS-. Correct polarity must be carefully observed. It is essential 
to use a twisted pair of wires for data BUS. Data communication and power 
supply of units are carried by one pair of wires, it is necessary to observe 
cross section of wires with regards to voltage drop and maximal consumed 
output.
CAPACITY AND CENTRAL UNIT
It is possible to connect two independent BUSes to the central unit CU2-
01M. Such connection is done by terminals BUS1+, BUS1- and BUS2+, BUS2-. 
It is possible to connect up to 32 units to each BUS. Total number of units 
connected directly to the CU2-01M is 64. Number of units can be further 
extended by unit MI2-02M, which can operate further two BUSes. MI2-02M 
is connected to the central unit CU by communication BUS TCL2. In total you 
can connect up to 2 MI2-02M units to one central unit.
SYSTEM COMMUNICATION BUS
The BUS has to be connected with a cable which is made of twisted pair of 
wires, with minimal cross section of wires 0.5 mm

2

. Shielded cable needs 

to be used in case the BUS cables are installed in an environment with a 
possibility of electromagnetic interference (e.g. in case of paralel-run with 
power line, close to electric machines and appliances, when passing Low 
voltage through a switchboard etc.).
The BUS cables need to be installed in accordance with its mechanic features, 
that are specifi ed by its manufacturer (into a conduit/rail, under a plaster, 
into a ground, hanging, etc.) To increase its mechanical protection we 
recommend installation of the cable into an electro-installation conduit of 
a suffi

  cient profi le. The total length of the BUS bar is 550 m for each BUS bar 

branch. The total length of the wiring using MI2-02M (where the maximum 
length of the TLC2 BUS bar is 300 m) may be extended to max. 850 m with 
optical fi bre extender. Topology of communication BUS is free except for 
circle topology.
POWER SUPPLY OF  THE SYSTEM
For power supply of the system we recommend to use power supplies of 
company ELKO EP: PS-50/27, DR-60-24, PS-100/iNELS. The number of power 
supplies in the system depends on the sum of the rated currents of the 
connected units with the corresponding reserve and max. current load on 
one BUS bar 1A. Installation of more power supplies on a large BUS eliminates 
voltage drop on a distant wires. When system of the electronic security 
signalisation is integrated, we recommend to use a backed-up power supply 
with a charger PS-100/iNELS in a cover with protective contact.
GENERAL INFORMATION
The unit is able to be operated without central unit but with very limited 
functionality. To use all the functions of the unit it is necessary to connect it 
to the central unit CU2-01M, or to a system that already contains this unit to 
extend system functions. All parameters are set by the central unit CU2-01M 
in software iNELS Designer and Manager.

PŘIPOJENÍ DO SYSTÉMU
Vodiče datové sběrnice systému iNELS se připojují na svorkovnici jednotky 
BUS+ a BUS-, přičemž není možné svorky vzájemně zaměnit. Pro datovou 
sběrnici je nutno použít kroucený pár vodičů. Datová komunikace i napájení 
jednotek jsou vedeny v jednom páru vodičů, přičemž je nutné dodržet průřez 
pro napájecí vodiče s ohledem na úbytek napětí na vedení a maximální 
odebíraný výkon.
KAPACITA A CENTRÁLNÍ JEDNOTKA
K centrální jednotce CU2-01M lze připojit dvě samostatné sběrnice BUS 
prostřednictvím svorek BUS1+, BUS1- a BUS2+, BUS2-. Na každou sběrnici lze 
připojit až 32 jednotek, celkově lze tedy přímo k centrální jednotce připojit 
až 64 jednotek. Další jednotky lze připojit pomocí jednotek MI2-02M, které 
generují další sběrnice BUS. Tyto se připojují k jednotce CU2-01M přes 
komunikační sběrnici TCL2 a celkem je možno připojit až 2 jednotky MI2-02M 
k CU2-01M. 
KOMUNIKAČNÍ SBĚRNICE SYSTÉMU
Sběrnice musí být provedena kabelem, který obsahuje kroucený pár vodičů 
pro datovou sběrnici systému s minimálním průřezem vodičů 0.5 mm

2

.  

Stíněný kabel je nutné použít v případě instalace kabelů sběrnice do 
prostředí s možností elektromagnetických interferencí (např. při souběhu se 
silovým vedením, v blízkosti elektrických strojů a přístrojů, při průchodu NN 
rozvaděčem apod).  
Sběrnicový kabel se instaluje v souladu s jeho mechanickými vlastnostmi, 
které udává výrobce (do trubky/lišty, pod omítku, do země, závěsný apod.) 
Pro zvýšení mechanické odolnosti kabelů doporučujeme vždy kabel 
instalovat do elektroinstalační trubky vhodného průměru.
Celková délka vedení sběrnice BUS jednotky CU2-01M je 550 m pro každou 
větev sběrnice. Celkovou délku vedení s použitím MI2-02M (kde je max. 
délka TLC2 sběrnice 300 m) je možné prodloužit na max. 850 m.
Topologie komunikační sběrnice BUS je volná s vyjímkou topologie kruhu.
NAPÁJENÍ SYSTÉMU
K napájení jednotek systému doporučujeme použít napájecí zdroje ELKO EP: 
PS-50/27, DR-60-24, PS-100/iNELS. Počet napájecích zdrojů v systému je dán 
součtem jmenovitých proudů připojených jednotek s odpovídající rezervou 
a max. proudovou zatěží na jedné BUS sběrnici 1A. Větší počet zdrojů na 
rozsáhlé sběrnici eliminuje také úbytek napětí na dlouhém vedení. Pokud je v 
instalaci použit systém elektrické zabezpečovací signalizace, doporučujeme 
použít zálohovaný zdroj PS-100/iNELS v krytu s ochranným kontaktem. 
VŠEOBECNÉ INFORMACE
Jednotka je schopna pracovat jako samostatný prvek bez centrální jednotky 
jen ve velmi omezeném rozsahu svých funkcí. Pro plnou využitelnost 
jednotky je nutné aby jednotka byla napojena na centrální jednotku systému 
CU2-01M, nebo na systém, který tuto jednotku již obsahuje, jako jeho 
rozšíření o další funkce systému.
Všechny parametry jednotky se nastavují přes centrální jednotku CU2-01M  v 
software iNELS Designer and Manager. 

Отзывы: