background image

 

 

  

Verze

 

02

‐ 

039/2011

 

Rev.:091013

 

                                                                              

Stránka

 

3

 

z

 

31

 

 
 

Connection Server Installation Manual 

 

1. Getting 

started 

  Commands are given in purple, e.g.: 

sudo reboot

 

  Paths and links are given in red: 

imm/Pictures 

  Notices are given in orange: 

No characters display when writing a password in 

terminal

 

  Tips and tricks are given in green: You do not want to run configuration via iMM CC at 

every server separately; as long as they are more, iMM CC can be enabled from any 

PC connected to local network… 

  Commands are in 

italic 

 

Important configuration commands in Linux: 

Ifconfig 

- finding IP address of station/server, similar to IPCONFIG in Windows 

mount

 – command for connection of certain device CD-ROM, network drive, etc.) 

umount 

- command for disconnection of certain device 

 

1.1. 

Putting Connection Server in run 

 

a)  Once you unpack Connection server, let the device stabilize at room temperature. 

b)  Insert attached SD card in the slot. 

c)  Connect the cabling (do not connect the supply yet):  

  Display HDMI device 

  LAN cable for ethernet port! 

  Keyboard to USB port. 

d)  After connecting the power supply (adapter with micro USB connector), Connection 

Server will start automatically. 

e)  When starting the system you can watch opening of individual services on the 

screen. Some services do not open, and display FAILD in red; in majority of cases it 

is not a problem; and has no influence whatsoever on the run of Connection Server.  

f)  When start of services is completed, only one line requiring login name will appear on 

the screen. 

 Alarmpi 

login: 

imm 

 

Password:

 imm123   

 

No characters display when writing a password in terminal 

 

Содержание Connection server

Страница 1: ...Version 02 039 2011 Rev 091013 Connection Server Installation Manual ...

Страница 2: ...ting 6 2 1 1 Bookmark Server 6 2 1 2 Bookmark Configuration 6 2 1 3 Bookmark A C 8 2 1 4 Bookmark Rooms 9 2 1 5 Bookmark Cameras 10 2 1 6 Calling between individual devices and sound 11 2 1 7 Phone settings 12 2 1 8 IP sound 14 2 1 9 Bookmark Energy 15 2 1 10 Bookmark Audit 19 2 2 Heating 20 2 3 Connection of Miele household appliances 21 3 Supplements 23 3 1 Export of configuration file to iMM 23...

Страница 3: ...ive etc umount command for disconnection of certain device 1 1 Putting Connection Server in run a Once you unpack Connection server let the device stabilize at room temperature b Insert attached SD card in the slot c Connect the cabling do not connect the supply yet Display HDMI device LAN cable for ethernet port Keyboard to USB port d After connecting the power supply adapter with micro USB conne...

Страница 4: ...ion but one should get familiarized with them and go back to them if a problem occurs 1 2 1 Change of password a Enter sudo passwd and confirm by Enter b You will be asked to enter the original password default is imm123 and confirm by Enter c Then enter a new password confirm by Enter repeat the new password and confirm by Enter No characters display when writing a password in terminal 1 2 2 Syst...

Страница 5: ...rk you can reset parameters of network setting or restart or use the Shutdown button to turn off Connection Server completely IP address is usually set static to avoid its change in time Network interface setting Button for complete shutdown Restart button IP address in sub network which iMM server is connected to Mask setting Default gate a DNS server ...

Страница 6: ... 2 1 1 Bookmark Server This bookmark contains control to virtual servers necessary for communication with CU applications and devices of third parties Within diagnostics the state of individual virtual servers can be revealed button Status suspend their run button Stop or turn them on button Start Servers are turned on automatically when Connection Server starts up Virtual server communicating wit...

Страница 7: ...n this case local address of Connection Server by entering 127 0 0 1 There you can also upload export pub exported from central unit Central unit IP address iMM server IP address Application licence Update settings Find file export pub Upload file export pub There are units events and variables from iNELS that are imported to iMM Save changes performed in the extract from file export pub ...

Страница 8: ...r Conditioning Units for connection Optional name of inner unit Selection of communication interface IP address of RS485 Ethernet t t Communication port of RS485 Ethernet converter Serves for entering central air conditioning address Creates defined air conditioning unit Seznam již definovaných klimatizačních jednotek Central air conditioning unit Selection of UID same as you selected for air IP a...

Страница 9: ... 1 4 Bookmark Rooms Serves for configuration of file rooms cfg which uploads iHC applications Read more in the manual for iHC application Name of new room Control of room will be protected by password Editing items in room Removal of room Password setting and change for access to room ...

Страница 10: ...from external network All cameras by Axis manufacturer with V2 and V3 protocol are supported further we support the below listed types of cameras AirLive WL2600 AirLive AirCam OD 600HD AirLive AirCam OD 325HD Planet ICA M220 ACTi ACM and the following types by company Vivotek FD 8134 FD 7132 PZ 7132 Select any camera name Camera IP address User name for access to camera Access password for camera ...

Страница 11: ...ounds from web interface webcamera or any IP camera For instance for 2n sound it will be stream e g rtsp 192 168 88 83 which consists of rtsp which is a kind of stream and sound IP address Once you set all calling devices save it by pressing Apply settings Note After clicking the Apply settings option configuration files of asterisk server will overwrite If you need own asterisk configuration do n...

Страница 12: ...eb interface e g SAMSUNGS3 Also the password must be identical with the one entered on the server Finally enter the IP address of Connection Server where you completed the settings In the application click on the intercom icon and then on Add contact Name the opposite station and enter its precise SIP name the name you entered on the server and then select Type of contact and select Save Naming th...

Страница 13: ... 091013 Stránka 13 z 31 Connection Server Installation Manual Sound settings Naming the sound in the h SIP name same as the one on the server Sound IP address Login name web sound interface Password for web sound interface ...

Страница 14: ... IP address from DHCP server is set on the new IP sound The assigned IP address of the sound has to be ensured in the abstract on router alternatively by means of software 2N Helios IP Network Scanner a Sign up to discovered IP sound via web interface Signup name admin Password 2n In the bookmark AdvancedSettings Network set fixed IP address from relevant range and sub network mask Entering login ...

Страница 15: ...gned to Watter Gas Electrical The setting of pulse conversion to unit of measure selection of currency and setting the currency unit is performed in iMMCC application in activated Energy module The Energy module allows recording of consumed energy for a day week month and year Data are saved in iMM Server the data do not get lost even in case of power shutdown or power cut Consumption can be displ...

Страница 16: ... electricity_VALUE It must be VALUE in the line Connection of energy meter Energy meter connects by means of a binary output unit Output from supported energy meter is distinguished to a that s why polarity has to be maintained by bringing minus to GND terminal and plus to IN terminal See 3 1 7 for settings Creation of counter Naming of counter Addition of further counters Bookmark System Bookmark...

Страница 17: ... Counter incrementing Action assignment to binary input where output from measuring instrument is connected Add action Energy upload Input of binary input unit where output from measuring instrument is connected User action selection Select uploading of required energy counter Select Increment counter ...

Страница 18: ...nter Switching of basic unit Number of impulses for given unit Price of one impulse Currency setting Selection of counters from file export pub For hot water consumption measurement For cold water consumption measurement For gas consumption measurement For electricity consumption measurement for up to 5 independent measurements ...

Страница 19: ...Stránka 19 z 31 Connection Server Installation Manual 2 1 10 Bookmark Audit Bookmark Audit serves for displaying and uploading LOG of events for diagnostic purposes When configuration in iMM CC is finished restart Connection Server ...

Страница 20: ...heating modes within given temperature program Minimum Inhibition Normal Comfort Auto If you wish to control individual heating modes you have to enable export of control and setting of heating program in IDM software In time weekly program administrator a part of export setting for visualisation Enabling export of heating circuits for visualisation ...

Страница 21: ... for XGW 2000 Setting the MieleGateWay IP address is recorded on iMM server in file etc imm miele where the basic shape is already set within the factory settings and only the IP address XGW 2000 has to be added in between the quotation marks In order to display the Miele control screen similarly as for energy management an icon referring to it has to be added on the Floorplan Adding the icon is r...

Страница 22: ...Verze 02 039 2011 Rev 091013 Stránka 22 z 31 Connection Server Installation Manual Basic Miele wiring Room name Naming of appliances ...

Страница 23: ...ntral unit Two files Export exp and Export pub will be created in selected folder the Export pub is important for upload in iMM Control Centre In case of large installation we recommend to use cutchoose program for export pub This program serves for trimming export pub only for useful and important elements and thus easier searching of elements in iMM floorplan in configuration If subtitles do not...

Страница 24: ...s Washing machines W 5967 WPS AutoDos W 5000 WPS Supertronic W 2859i WPM Integrated steam ovens DG 5080 DGC 5080 XL DGC 5085 XL Glass ceramic cooking hotplates KM 6202 KM 6204 KM 6212 Driers T 4859 Ci T 8969 WP EcoComfort T 8001 WP Supertronic Dishwashers G 5930 SCi G 5935 SCi XXL G 5980 SCVi G 5985 SCVi XXL Coffee makers CVA 5060 CVA 5065 ...

Страница 25: ...5080 B Induction cooktops KM 5956 KM 6314 KM 6315 KM 6317 KM 6346 KM 6352 KM 6354 KM 6380 KM 6382 KM 6383 Kitchen aspirators DA 420 4 DA 420 V DA 424 V DA 430 4 DA 5000 D DA 5100 D DA 5294 D DA 5320 D DA 5330 D DA 5590 D DA 5620 D DA 6290 D DA 6590 D DA 6520 D DA 249 4 DA 289 4 DA 439 DA 489 4 DA 5190 W DA 5294 W DA 5320 W DA 5390 W DA 5590 W DA 5690 W DA 6000W DA 6290 W DA 6590 W ...

Страница 26: ...tion 1 Connect all by the attached wiring scheme 2 Set the RS232 ETHERNET converter 3 Set the central address on the wall air conditioning unit control 4 iMM communicates via converter Papouch GNOME RS232 and its IP address has to be entered in file etc imm coolMaster cfg together with the type of the CoolMaster control unit If everything is set correctly the CoolMaster display will not show U00 G...

Страница 27: ...Verze 02 039 2011 Rev 091013 Stránka 27 z 31 Connection Server Installation Manual Setting the RS232 ETH converter ...

Страница 28: ...s and hold down for 5 seconds the TEST button Setting mode 00 shows in the middle and GROUP and the number on the left GROUP should flash if not press the on off key then it should flash Select the desired central address using the time setting button Confirm by pressing the on off button Complete settings by TEST button ...

Страница 29: ...en worked on We support communication of LG air conditioning units which is marked as PI485 Any LG unit supports that interface it can be interconnected to application iTP via iMM b Indirect connection means utilization of communication unit CoolMaster which can communicate with different types and makers of air conditioning units http www inels cz media PDF export download Coolmaster_compatibilit...

Страница 30: ...dress inside the unit using buttons for temperature setting Press ON OFF for directing to the inner unit Address displays on the unit To finish the setting reset the control To check the address RESET PLASMA 3 Set the converter 4 Add the air conditioning unit in clims in iMM web interface see 2 1 4 5 Add air conditioning units in rooms in iMM web interface see 2 1 5 2 1 5 Setting the 485 ethernet ...

Страница 31: ...Verze 02 039 2011 Rev 091013 Stránka 31 z 31 Connection Server Installation Manual ...

Отзывы: