Electrical Requirements
For your own safety, we recommend that your cooker is installed by a competent
person such as one who is registered with NICEIC (National Inspection Council for
Electrical Installation Contracting). The cooker should be installed in accordance with
the latest edition of the IEE Regulations.
Warning: This appliance must be earthed.
Electrical Connections
The installer must check that the voltage shown on the rating plate corresponds with
the house electricity supply.
The cooker must be supplied via a suitable double pole isolating switch, having a
contact separation of at least 3mm in all poles placed in a readily accessible position
adjacent to the cooker.
If the cooker is to be wired into a connector unit, this may be positioned behind the
cooker providing the following requirements are met:
i) The connector unit must not project from the wall more than 25mm.
ii) The top of the connector must not be more than 130mm above floor level.
Remove the terminal cover at the rear base of the cooker. Pass the cable through the
cable clamp and connect to the appropriate terminals provided.
Allow sufficient cable for any future servicing.
Tighten the screws on the cable clamp and replace the cover.
Make main connections in the connector unit or cooker control unit.
This appliance conforms to B.S. EN 55014 regarding suppression of Radio and
Television reception interference.
A double Pole control switch having a minimum rating of 32 amps should be used to
feed the cooker using a suitably rated cable.
Where a hob is fitted adjacent to or over the cooker, a 45 amp Double Pole control
switch should be used to feed both units via separate suitably rated cables.
We recommend a minimum of 4mm
2
PVC insulated twin and earth cable conforming to
B.S. 6004 for connection of each appliance.
In all cases adhere to routing details (see fig. 4).
This appliance must not be installed over any other appliance that generates heat
such as a plinth heater
Installation
41
Note: Due to many different types of installation, a mains cable is not
supplied with this product. The installer will fit the correct type and length of
cable.