VE150 Cooling Unit
23
Problems
Reasons
Possible Issue /
Check
Solution
Notes
The Cooling Unit
does not start -
the Unit worked
The main supply
voltage is too low
Electrical
connection
Check the wire
connection
Check the voltage
The wires are
oxidized
Thermostat
Thermostat is
broken!
Faulty electronic Unit
Everything is well
installed, gas inside
the system, no cool at
all (rare case)
Power consump-
tion greatly in-
creased, constant
pressure in the
system
Replace the com-
pressor
The Cooling Unit
works for few
seconds - the Unit
worked
The Cooling Unit
works but it is not
cooling -
The Unit is new
The Cooling Unit
keeps working
The cabinet is too big
Check the cabinet
dimension and
compare it to the
maximum cooling
capacity of the
unit.
Is the correct unit
installed in the
cabinet?
You have wrong cool-
ing unit!!!
Thermostat not in-
stalled on the evapo-
rator or installed in
the wrong position
Check if the probe
is installed on the
evaporator or if
it is in a different
socket
Place the probe in the
appropriate socket
Humidity inside the
cabinet
Humidity gets
inside the cabinet
by passing through
gasket or pipes
hole through the
cabinet.
Ice presence all
over evaporator
Find where humidity
gets inside from.
Содержание Isotherm VE150
Страница 2: ......
Страница 6: ...6 VE150 Cooling Unit SCHEMA ELETTRICO AC DC...
Страница 17: ...VE150 Cooling Unit 17 WIRING DIAGRAM AC DC...
Страница 28: ...28 VE150 Cooling Unit SCHEMA ELECTRIQUE AC DC...
Страница 39: ...VE150 Cooling Unit 39 SCHALTPLAN AC DC...
Страница 50: ...50 VE150 Cooling Unit ESQUEMA EL CTRICO AC DC...
Страница 58: ......
Страница 59: ......