VE150 Cooling Unit
Trouble Shooting
Problems
Reasons
Possible Issue /
Check
Solution
Notes
Air cooled
The Cooling Unit
does not start -
the Unit is new
The main supply volt-
age is too low
The unit is not
connect or wrong
polarity
Check the wire con-
nection
Check the section
of wires between
battery and elec-
tronic unit
101N0210.pdf
Check the voltage
on the connection
right before the
Electronic Unit, the
voltage must be
between 10.5 V to
13.5 V for battery
at 12 VDC and 21
to 27 for battery at
24 VDC
Recharge the battery -
If the battery is older
than 3 or 4 years it
could be necessary to
replace it!
The wires are
oxidized
Replace the wires
Thermostat
The thermostat is
not connected
Check the correct
connection of the
thermostat on the
electronic unit and on
the thermostat.
Thermostat is
broken!
Bridge C and T con-
nections, on the
electronic unit.
The unit works.
Replace the ther-
mostat
Faulty electronic Unit
(rare case)
Bridge C and T con-
nections, on the
electronic unit.
The unit does not
start even if the
voltage is correct.
Replace the electronic
unit
Cooling Unit works
for a short period
of time
Not enough venti-
lation around the
condenser
Remove the fridge
from its place and
turn it on, if it keeps
cooling, improve the
ventilation!
Содержание Isotherm VE150
Страница 2: ......
Страница 6: ...6 VE150 Cooling Unit SCHEMA ELETTRICO AC DC...
Страница 17: ...VE150 Cooling Unit 17 WIRING DIAGRAM AC DC...
Страница 28: ...28 VE150 Cooling Unit SCHEMA ELECTRIQUE AC DC...
Страница 39: ...VE150 Cooling Unit 39 SCHALTPLAN AC DC...
Страница 50: ...50 VE150 Cooling Unit ESQUEMA EL CTRICO AC DC...
Страница 58: ......
Страница 59: ......