The following are the menus which can be modified:
P0
- Timer (MIN and AUTO modes)
In MIN and AUTO mode, the system’s default setting is
6 hours
of
continuous operation. The default value can be changed in this menu.
The choice range is between
1
and
99
hours.
P1
- Timer (MAX mode)
In MAX mode, the system’s default setting is
4 hours
of continuous
operation. The default value can be changed in this menu. The choice
range is between
1
and
99
hours.
A2
– Centigrade and Fahrenheit
degrees
The system’s default setting is
Centigrade
degrees
. This menu allows
you to change the parameter to
Fahrenheit degrees
.
A3
- Offset
This refers to the temperature difference detected by the probe and the
temperature shown on the display. This menu allows you to change this
value from
-9°C
to
+9°C
with
1°C
increments.
A4
- Max condenser fan speed
The cooling fan’s speed is variable and depends on the operation of the
compressor. Its default setting is
100%
of its operational power. Its
maximum speed can be reduced (for example if it is too loud) according
to the following table. Bold values are its default settings.
WARNING: if the selected speed value is too low, the compressor
may overheat and the device may shut itself down (see error table –
code
E3
–
E4
–
E5
).
Level
Percentage
10
100%
9
90%
8
80%
7
70%
6
60%
5
50%
4
40%
A5
– Battery saver value
Its default setting is
10.8 Vdc
(Cut-out) and
12 Vdc
(Cut-in). This menu
allows to change the values according to the following table. Default
values are in bold.
Vm
12Vdc
Vm
12Vdc
Cut-out
Cut-in
Cut-out
Cut-in
0
9.8
12.5
10
9.8
12
1
10
11
10
2
10.2
12
10.2
3
10.4
13
10.4
4
10.6
14
10.6
5
10.8
15
10.8
6
11
16
11
7
11.2
17
11.2
8
11.4
18
11.4
9
11.6
19
11.6
E
N
GL
ISH
39