background image

 

2

Mechanical Instructions 

 
Site Selection  
 
Review the NEMA Type rating of the heater noted on the 
INDEECO Application Data.  Do not install a heater in an 
area not consistent with its rating. 
 
Allow sufficient free space around heater installation site. 
Work space for heater maintenance should be at least three 
feet in front and on either side of the heater.  The minimum 
pull space for the Immersion Heater installation or removal 
from the vessel should be at least equal to length between 
the inlet and outlet nozzle plus two feet. 
 
Electric heaters are capable of developing high 
temperatures.  Therefore, extreme care should be taken to 
avoid mounting heaters in an atmosphere containing 
combustible gases, vapors, dusts, or fibers unless properly 
marked as suitable for the condition. 
 
Heater Orientation 
 
This heater has been constructed for a specific mounting 
orientation.  It must be mounted in this manner, to prevent 
improper operation or damage. Refer to the INDEECO 
Application Data for the correct mounting figure number. 
 
The location selected must be capable of safely supporting 
the heater’s weight plus the fluid weight. 
 
Mount the heater with structural quality bolts matching the 
holes provided in the mounting feet.  When Figure 23 
(Vertical Floor Mounting) is provided, the mounting 
channels must be drilled by the user.  Where slotted holes 
are provided, install the bolts to the outside of the slots to 
allow the heater to thermally expand. Mount on a smooth 
surface.  Do not use lock washers, and apply minimum 
torque necessary to contain the equipment but not prevent 
expansion on bolts in slotted holes.   
 
The heater should be mounted plumb horizontally and 
vertically to assure proper flow and avoid draining or venting 
problems. 
 
Pipe the incoming fluid connection to the nipple marked 
"Inlet".  Pipe the hot outgoing connection from the nipple 
marked "Outlet".  The inlet and outlet references on the 
attached figures are shown as the INDEECO standard 
arrangement.  The actual markings on the heater may be 
reversed.  Do not operate the heater with a flow direction 
different from the nozzle markings without approval from 
INDEECO.  The heater may include instruments that will not 
operate properly if the flow direction is reversed. 
 
Note that customer piping must be supported to minimize 
nozzle loading on the heater inlet and outlet.  Consider 
using expansion joints or flex hoses to allow connections at 
the slotted end of the heater to move with the heater.  
Failure to do so may result in damage or leaking of the 
heater vessel. 
 
 

Thermal expansion of the heater can be approximated as: 
 

Nozzle to 

Nozzle length 

(Inches) 

x .00001 x 

Operating 

Temp (

q

F) 

- 70

q

With liquid systems, the customer piping must be routed 
and piped to ensure proper venting of the heater.  Trapped 
pockets of air will result in improper operation and potential 
heater damage.  High points must be vented and low points 
drained to allow equipment maintenance.  A low point drain 
plug is provided in the heater to allow draining. 

The heater is designed for operation at specified design 
flows.  When flow rates are not defined, the general 
requirement is to limit flow velocity to 10ft/sec for liquids or 
keep the density (#/ft

3

) x velocity (ft/sec) <10,000 for gases.  

Customer piping size should match the inlet/outlet of the 
heater to meet this requirement unless otherwise noted.  
 
If the heater is installed in a pressurized system, a relief 
valve must be installed at the outlet of the heater.  A 
pressure relief valve may be sufficient, unless local codes 
require a pressure-temperature relief valve.  As a minimum, 
the valve must be sized to relieve at a rate equal to the rate 
that the heater can thermally expand fluid trapped in the 
heater due to downstream blockage. 
 
DO NOT place a shutoff of any type between the pressure 
relief valve and the heater, or on discharge pipes between 
the relief valve and the atmosphere. 
 
On heaters with ANSI flanged inlet/outlets, take care to 
prevent scratching the flange faces.  Select a gasket rated 
for the application service and temperature and pressure. 
 
Clean and flush system prior to initial startup to remove 
contamination generated during fabrication.  Provide filters 
or strainers on liquid systems as required. 
 
Insulation 

 
 
 
 
 
 

Insulation is typically provided only on the heater shell by 
INDEECO.  The customer may prefer to add additional 
insulation to the Immersion Heater flange or bottom head of 
the vessel for added personnel safety and energy 
conservation. 
 
 
 
 
 
 
 
 
Insulation used on heating systems with flammable liquids 
should utilize closed cell insulation to reduce fire hazards 
caused by absorption of leaks. 

WARNING 

On heaters with extended terminal boxes and exposed 
element tubes, do not insulate more than 2” above the 
Immersion Heater flange. Dangerous over-heating of 
the terminal box wiring could result.

 

WARNING 

Some surfaces of the heater vessel or Immersion 
Heater may be extremely hot.  Avoid contact to prevent 
personnel injury or fire.

 

Отзывы: