Emergency Lighting System 

INSTALLATION MANUAL

Содержание FIREscape

Страница 1: ...Emergency Lighting System INSTALLATION MANUAL ...

Страница 2: ...Page 4 of 56 FIREscape System Installation Manual Title FIREscape System Installation Manual Issue 1 0 Issue Date February 2017 Part No 2 3 0 1331AS ...

Страница 3: ...L RS 232 Isolator 20 9 3 EL ISOL Connection 21 9 4 Additional Port PRN 21 10 Addressable Emergency Lighting Lines 22 10 1 Principle 22 10 2 Mounting Base EL TSB 22 10 3 Emergency Lighting LineConnection 23 11 Wiring to House Lighting via PM 25 12 Emergency Luminaires 27 12 1 EL DL2 AS Escape Corridor Down Light 27 12 1 1EL DL2 AS Technical Specifications 27 12 1 2EL DL2 AS Classifications Mounting...

Страница 4: ...cal Specifications 37 14 EL EXP Expansion Unit 38 15 TCH B200 Address Programming Device 40 15 1 Button Functions 40 15 2 Programming 40 16 Cabling Length 41 16 1 Illumination Points 41 16 2 Using the Cabling Recommendations Graphs 41 16 3 Illumination Points at Regular Intervals 43 16 4 Examples 43 16 5 Other Devices 46 16 6 Devices at Equal Intervals 48 16 7 Devices at the End of The Cable 51 17...

Страница 5: ... and given an address on the system to be easily identified This address consists of a line number and a device number The Hochiki FIREscape range includes 16 meter to 24 meter range of emergency exit signs with the ability to be either wall or ceiling mounted single sided or double sided The emergency escape luminaires also come in various transverse C0 and longitudinal C90 planes to best suit bu...

Страница 6: ...ding earth must be 1 M If the insulation resistance is smaller uncontrolled ground currents will transfer to the system and cause interference Problems are caused for example when the shield cable is terminated to metal installation boxes which are bonded to the building earth All shield cables must be connected to the control panel housing Similarly the shield cable at the keypad end must be conn...

Страница 7: ...trol panel is approximately 8 kg including 1 x 7 Ah battery The weight of the control panel must be considered when for wall mounting The cable between the control panel and the transformer must not exceed 1 m The cable is provided with the control panel Figure 2 An example installation Drill 4 x 6mm holes for the mounting plugs The hole depth must be 20 25 mm Refer to Figure 3 on page 8 for the l...

Страница 8: ...wall and guide the screws into the screw grooves in the housing Tighten the screws Route the cables between the wall and the panel housing and then through the cable aperture in to the panel housing Shorten the cables to a suitable length Strip the cables ready for connection The insulation resistance must be measured before connecting the cable connectors ...

Страница 9: ...8 keypads can be connected to the system The keypads are rear entry only by connection and connect directly to the CPN serial communication port of the motherboard A 4 core cable plus SHEILD is required for the connection of a keypad to the control panel The keypad can be powered directly from a local power supply or the control panel s auxiliary supply The local power supply must be double insula...

Страница 10: ... cabling can be a star through a central node or ring through each device The units do not have to be addressed sequentially Figure 11 EL KP Keypad Connectivity NOTE The maximum length of the data bus is 500m When calculating the voltage drop the maximum power consumption of the keypad must be used Figure 12 EL KP Dimensions ...

Страница 11: ...the location of the holes see Figure 14 Attach the plugs Take the cable through the bottom plate There is a pre scored section at the top of the casing for surface installation This should be snapped off and filed if it is required Attach the base plate with 4 x 3 9 mm screws Shorten the cables so that they are suitable for installation Strip the cables for connection Connect the 5 pin connector a...

Страница 12: ... the keypad to the base plate with 3 mm machinescrews The front cover fixing screw is concealed with the supplied self adhesive cover sticker 6 1 Connection Figure 14 Keypad Connector Description EL 2 EL KP Data RS485 A X1 8 1 Data RS485 B X1 7 2 Voltage X1 6 3 Voltage 12VDC X1 5 4 Cable shield Connection point for the control panel housing s cable shield 5 ...

Страница 13: ... of the keypad is set with the rotary switch SW1 Connect the 5 pin plug into connectorX2 Adjust the display contrast if necessary after applyingpower Attach the keypad to the base plate with 3mm machinescrews Address SW1 backlight off SW1 backlight on 1 0 8 2 1 9 3 2 A 4 3 B 5 4 C 6 5 D 7 6 C 8 7 F ...

Страница 14: ...for example Addr 1 along with the software version and the text Polling OK on the bottom row The text will change to If there is a problem with the data connection the display will read after which the keypad will restart This will be repeated until the connection works For information on troubleshooting data connection problems see the section Troubleshooting on page 49 KLG remote panel c 2005 Oy...

Страница 15: ...d Connections 8 1 Control Panel Fuses Description Fuse Value A Points Connector 35 VAC F1 6 3 1 2 X8 Batteries 12VDC F2 6 3 1 2 X5 Voltage for external devices F3 0 5 1 3 2 4 X1 Voltage for external devices F4 0 5 5 9 6 X1 Voltage for bus A F5 2 5A 1 3 2 4 X2 Voltage for bus B F6 2 5A 5 7 6 8 X2 ...

Страница 16: ...T1 Relay C 1 14 X1 EXT1 Relay NC 1 15 X1 EXT1 Relay NO 1 16 X1 FAIL Relay C 1 17 X1 FAIL Relay NC 1 18 X1 FAIL Relay NO 1 19 X1 8 3 LEDs The LEDs on the motherboard indicate functions and serial communication RX indicates serial communication reception red TX indicates serial communication transmission green CPN green TX Data sent from CPN port NL KLG PRN red TX Data sent from PRN port PRG red RX ...

Страница 17: ...mpers 1 3 The following settings are possible Language 1 2 3 English ON ON OFF Finnish ON OFF OFF Swedish OFF ON OFF Norwegian OFF OFF ON Test mode ON ON ON 4 8 Factory Reset The control panel can be initialised with factory settings Short the RESET pins Short the language selection pins 1 2 3 Press and hold down the cover switch Open the RESET pins Release the cover switch ...

Страница 18: ...PC printer the connection may cause interference due to earth leakage This is because the negative pin of the RS 232 connector is usually connected to shield ground The connection must be arranged through a local modem or the EL ISOL unit if the RS 232 device and the control panel are not connected to the same power supply group Usually this means the same room In no instance should the cable leng...

Страница 19: ...FIREscape System Installation Manual Page 21 of 56 9 3 EL ISOL Connection Figure 19 EL ISOL Connection 9 4 Additional Port PRN This port can be used for connecting external RS 232 devices ...

Страница 20: ... each lighting line is 1 km and the maximum loop resistance of the conductors is 74 Ω The cable s conductor capacitance must be 0 7 µF The power consumption also restricts the cable distance A maximum of 127 units can be connected to a single lighting line depending on the power consumption of the unit 10 2 Mounting Base EL TSB The mounting base required for the luminaires is the Hochiki EL TSB st...

Страница 21: ...3 Emergency Lighting Line Connection Figure 5 Wiring the Lighting Line Cable to an EL TSB Mounting Base The lighting line cable is taken to each line device The lighting line cabling can be a star through a central node or a ring through each mounting base ...

Страница 22: ...FIREscape System Installation Manual Page 24 of 56 Figure 6 An example of a spur arrangement ...

Страница 23: ...l Page 25 of 56 11 Wiring to House Lighting via PM There are many ways from which to wire and monitor house lighting Figure 7 is a typical example of how to do this Figure 7 An example of a typical connection to a single lighting circuit ...

Страница 24: ...when live closing its relay contacts The EL2 s 40v line output from either lines A or B terminals are to spur to each lighting circuit s phase monitor The from line A or B shall feed in through terminal 15 of the EL PM and out of the terminal 18 From terminal 18 the shall feed into the FIREscape emergency lighting connector block where it will be accompanied by the from either line A or B From the...

Страница 25: ... EL DL2 AS Technical Specifications Classification C0 C2 C90 E25 Ordering code EL DL2 AS Operating Voltage 24v 40v Minimum Standby Operating time 3 Hours Power consumption from line W 0 1 Watt Battery 7 4v 450mAh 3 33Wh Dimensions mm 100 diameter x 48 height inc 8mm for EL TSB base Weight including battery g 100g Temp Range 40 C Fire class UL94 V O Case material Fire resistant PC ABS plastic FR301...

Страница 26: ...0 E6 3 Ordering code EL DL3 AS Operating Voltage 24v 40v Minimum Standby Operating time 3 Hours Power consumption from line W 0 1 Watt Battery 7 4v 450mAh 3 33Wh Dimensions mm 100 diameter x 48 height inc 8mm for EL TSB base Weight including battery g 100g Temp Range 40 C Fire class UL94 V O Case material Fire resistant PC ABS plastic FR3010 Case color White RAL 9003 Signal White Compliance AS2293...

Страница 27: ...e of 16 meters There are various models each with a different arrow direction indicating the direction of an exit Note the direction of the LEDs and alignment rib on the cup of the exit sign in relation to the alignment rib on the mounting base when installing EL 16G R AS Orientation of EL 16G AS Orientation of EL 16G L AS Orientation of EL 16G R AS ...

Страница 28: ...v Minimum Standby Operating Time 3 Hours Power consumption from line W 0 4 Watt Battery 7 4v 450mAh 3 33Wh Dimensions mm including base Wall mounted 204L x 133H x 81 3D Ceiling mounted 204L x 201 5H x 32D Weight g 150g Temp Range 40 C Material Cup and bracket Fire retardant Lens Acrylic Fire class UL94 V O Case color White RAL 9003 Signal White Compliance AS2293 AS NZS 60598 2 22 EN55015 IP Rating...

Страница 29: ...f 24 meters There are various models each with a different arrow direction indicating the direction of an exit Note the direction of the LEDs and alignment rib on the cup of the exit sign in relation to the alignment rib on the mounting base when installing EL 24G R AS shown Orientation of EL 24G AS Orientation of EL 24G L AS Orientation of EL 24G R AS ...

Страница 30: ...vet Assy Operating Voltage 24v 40v Minimum Standby Operating Time 3 Hours Power consumption from line W 0 4 Watt Battery 7 4v 450mAh 3 33Wh Dimensions mm including base Wall mounted 204L x 133H x 81 3D Ceiling mounted 204L x 201 5H x 32D Weight g 150g Temp Range 40 C Material Cup and bracket Fire retardant Lens Acrylic Fire class UL94 V O Case color White RAL 9003 Signal White Compliance AS2293 AS...

Страница 31: ...sification C0 E40 C90 E40 Ordering code NF89 O AS Operating Voltage 24v 40v Minimum Standby Operating time 3 Hours Power consumption from line W 0 6 Watt Battery 7 4v 2950mAh 21 46Wh Dimensions mm 100 diameter x 65 height inc 8mm for EL TSB base Weight including battery g 190g Temp Range 40 C Fire class UL94 V O Case material Aluminum Case color White RAL 9003 Signal White Compliance AS2293 AS NZS...

Страница 32: ...tions Classification C0 D6 3 C90 D32 Ordering code NF89 C AS Operating Voltage 24v 40v Minimum Standby Operating time 3 Hours Power consumption from line W 0 6 Watt Battery 7 4v 2950mAh 21 46Wh Dimensions mm 100 diameter x 65 height inc 8mm for EL TSB base Weight including battery g 190g Temp Range 40 C Fire class UL94 V O Case material Aluminum Case color White RAL 9003 Signal White Compliance AS...

Страница 33: ...his unit is installed in a deep back box not supplied which can be surface or flush mounted The unit is addressed using the TCH B200 Hand Held Programmer in conjunction with a programming lead 12 7 1 EL SL Technical Specifications Ordering code EL SL Operating voltage Vd c 24 40 Power consumption from line W 0 5 10 Batteries V mAh 9 200 Dimensions mm 70H x 70W x 65D Ingress Protection Rating IP44 ...

Страница 34: ...N O normally open or N C normally closed The EL IO can be configured in the following 2 options 4 x Un monitored NO NC inputs or 2 x Monitored NO NC inputs EL IO The 2 outputs can be used to control traditional luminaires and can be activated using the system cause and effect programming The output state is shown with a green LED OUT1 OUT2 If an output is activated the LED is illuminated NOTE Thes...

Страница 35: ...REscape System Installation Manual Page 37 of 56 Figure 10 EL IO Wiring Connections 13 1 1 EL IO Technical Specifications Unit EL IO Operating Voltage VDC VAC 24 40V Power consumption from line NU 2 0 1W ...

Страница 36: ...before installing the chip Note the orientation of the chip the groove must point to the right toward the SER1 2 connector The card has 2 serial communication ports which can be configured either as RS 232 or RS 485 ports The selection of the port s serial communication format is done by setting all jumpers 4 that refer to the port A or B to the 232 setting for RS 232 or 485 for RS 485 The port wi...

Страница 37: ...FIREscape System Installation Manual Page 39 of 56 Figure 20 EL EXP Connection ...

Страница 38: ...nment rib this should be at approximately 6 on a clock face Twist the FIREscape device clockwise until it locks in place Press the left button on the programmer The programmer reads the FIREscape device s address and this is displayed on the numeric LEDs The factory preset address is 127 Set the address with the left 10s and right units buttons Set the displayed address into the FIREscape device b...

Страница 39: ...f the luminaires is presented in the technical specifications section see Technical Specifications on page 46 For cabling the luminaires power consumption is divided into units of 50 mW each The power requirement unit is referred to in this manual as an NU The cabling examples use a 1 5mm The number of necessary conductor pairs can be derived from the power consumption of the luminaire points and ...

Страница 40: ...y Total mA Total FU STEP LIGHT 0 7 8 5 0 0 STEP LIGHT 1 12 8 8 0 0 STEP LIGHT 2 15 6 9 0 0 STEP LIGHT 3 16 8 10 0 0 STEP LIGHT 4 23 6 14 0 0 STEP LIGHT 5 37 3 22 0 0 STEP LIGHT 6 50 30 0 0 STEP LIGHT 7 78 47 0 0 3 3 2 0 0 Type Current mA FU Max Line Device Quantity Total mA Total FU I O UNIT 3 3 2 0 0 Factory default and I O unit NO OUTPUTS I O UNIT 15 6 9 0 0 when using the output relays of the I...

Страница 41: ...mented as follows KLMA 2x0 8 74ohm km Devices placed on cable at regularintervals 1750 1750 1500 1270 1270 1000 2 conductor pairs LOOP 1 5 875 750 800 635 1 conductor pair RADIAL 0 8 620 500 400 310 0 100 200 300 400 500 600 700 800 900 1000 NOTE 1 Conductor Pair 0 8 CableRadial 2 Conductor Pair 1 5 Radial or 0 8 Loop Single Storey Building Luminaires Branch 1 Luminaires Branch 2 A building with t...

Страница 42: ...h 2 A building with the size 50 x 300 m EL 2 Control Panel using line A 87 pcs EL 16 AS 16m signs 10NU Power requirement 870NU 40 pcs EL 16 AS 16m signs 10NU Power requirement 400NU Total power requirement 1270NU We can implement the cabling if the power requirement of each branch remains under 875NU Figure 23 ...

Страница 43: ...ugh the length of the floor and branching there to different spaces The distance to the furthest luminaire is approximately 20 70 m 90 m The riser cable between the floors conveys twice the number of power units compared to the floor Because the riser is rather short this is not of real significance Considering this we can inspect each floor as a separate cable noting that the total power consumpt...

Страница 44: ... Try to locate the device that requires the greatest voltage at the beginning of the cable If the cable has devices operating at different minimum operating voltages the cabling can be calculated by estimating each device separately However you need to know the total power consumption of the cable The cable type is MHS 188 Ω km Example 1 2 pcs EL KP maximum current requirement 60 mA minimum operat...

Страница 45: ... The keypads are in a different building for example at the end of the cable The current in the cable between the device x EL KP 1 and the control panel is a maximum of 60 60 mA 120 mA The voltage requirement is 8 V Figure 26 The graph shown in Figure 32 on page 45 indicates that two conductor pair can supply the voltage to the keypad ...

Страница 46: ...FIREscape System Installation Manual Page 48 of 56 16 6 Devices at Equal Intervals Minimum Operating Voltage 6 5 V Figure 27 ...

Страница 47: ...FIREscape System Installation Manual Page 49 of 56 Minimum Operating Voltage 7 5 V Figure 28 ...

Страница 48: ...Page 50 of 56 FIREscape System Installation Manual Minimum Operating Voltage 8 5 V Figure 29 ...

Страница 49: ...FIREscape System Installation Manual Page 51 of 56 16 7 Devices at the End of The Cable Minimum Operating Voltage 6 5 V Figure 30 ...

Страница 50: ...Page 52 of 56 FIREscape System Installation Manual Minimum Operating Voltage 7 5 V Figure 31 ...

Страница 51: ...FIREscape System Installation Manual Page 53 of 56 Minimum Operating Voltage 8 5 V Figure 32 ...

Страница 52: ...C Mains AC in minimum 230 VAC 15 VAC 195 5 Mains AC in maximum 230 VAC 10 VAC 253 Maximum battery capacity Ah 7 Battery charge current A 0 4 Battery charge voltage V 20 C 13 8 Voltage outputs V Minimum voltage 10 0 Maximum voltage 14 5 Normal ripple from nominal voltage mV 50 Maximum ripple from nominal voltage mV 50 12 VDC F3 A 0 5 12 VDC F4 A 0 5 Total A 0 6 Current consumption motherboard mA 60...

Страница 53: ...40 48 5 48 5 10 5 15 35 x 43 x 22 EL ISOL RS232 isolator 5 40 50 50 8 15 37 x 69 x 30 EL EXP Serial communication expander 5 40 10 15 8 15 51 x 66 x 30 EL DL2S Safety light 10 50 4 20 40 99 7 x 48 diameter x depth EL SL Step light 10 50 10 20 40 70 x 70 x 65 EL IO Input output unit 10 50 2 20 40 108 x 108 x 32 At default light level 4 18 1 Luminous Intensity for Exit Signs Figure 33 Adjusted light...

Страница 54: ...e 56 of 56 Type 16M 24M Luminous Intensity NU Cd NU Cd 0 4 0 0 4 0 0 1 6 0 9 7 0 4 2 7 1 6 10 0 7 3 8 2 0 16 1 3 4 10 2 6 23 2 0 5 13 3 7 28 2 5 6 7 0 33 3 0 7 Power from battery 9 0 Power from battery 3 2 Factory setting for normal intensity ...

Страница 55: ... control panel In other cases the RS 232 device s must be isolated from the control panel with an isolator card Measure the earth leakage by disconnecting the directly connected RS232 device s from the system After this use a voltmeter in the DC range and measure each connection point against building earth The meter must show 0V 19 3 Luminaire Line 19 3 1 Supply Current The current can be determi...

Страница 56: ...pad reports a double address it means that more than one device is using the same address The luminaires are supplied already set to address 127 You need to program the luminaires with unique addresses before installing Failure to do this will result in a double address situation Luminaires with a double address can be located for example by setting them active or blinking etc In a double address ...