Make sure that each wire is stripped-and-tinned to .025 in.
l
Make sure that each wire is tightly screwed into the terminal strip.
l
Make sure that each wire is touching the terminal strip. If the plastic wire jacket is clamped into the terminal strip,
connections will not be made.
l
Clip or cap any unused wires.
l
Make sure that ribbon cables and the coin cell battery are secure.
AC Electrical Connections
Danger—Make sure that power to the controller is disconnected before making any wiring connections.
Connexions Aux Courant Secteur/Alternatif
Danger—Débrancher toute alimentation à l'appareil avant de connecter les fils.
Pin
Description
North American Wire Color
European Wire Color
L
Line
Black
Brown
N
Neutral
White
Blue
Protective Earth
Green
Green and yellow
AC Wiring Description
Figure 4.1 Protective Earth ground screw location and connection