IN-COMMAND NCSP35 Скачать руководство пользователя страница 8

 

Please review the NCSP35 User Manual for further HVAC operational 
instructions.  You can scan the QR code shown below or use the 
following link:  

https://in-command.net/wp-

content/uploads/2018/08/owners-manual_ncsp35.pdf

 

 

 

 

Troubleshooting 

HVAC 

 

(Dometic Systems) If the room temp reads 100F, remove the room 
sensor cover and pull the room sensor out of the holding clip.  The 
temp should read normally.  Adjust the holding clip down on the 
room sensor so that it is not pinching it.  

 

(RVP Systems) If the room temp reads 111F, the room sensor was 
connected to the cool shed connections on the RVP control box.  
Swap the wires between the cool shed and room sensor pins.  The 
room temp should start reading correctly without a reset. 

 

(Both Systems)If no HVAC function, check to see if the room (zone) 
temp is blank.  If it is, make sure the RV-C cables are connected to 
the gateways and make sure there is an EOL (End of Line) 
terminator resistor at the last gateway in the line.  Make sure the 
address on the gateway is correct.  If that is correct, redo the 
power, ground and communication wires between the gateway and 
control box.  Verify the gateway has 12VDC. 

 

(Dometic)If there are multiple rapid clinking sounds when operating 
the furnace function, the gateway has old software and needs to be 
swapped out. 

 

(Dometic)If a zone will not change functions (i.e. stuck on furnace 
mode), try adjusting the fan speed.  Most likely it will show Auto, try 
and get it to either low or high.  This indicates the gateway is in a 
locked state.  If you can get the fan mode to change, you should 
then be able to change the zone function to off.  Once it stays in off 
mode, try power cycling the system. 

 

If changing an HVAC function in a Zone, and the function changes in 
a different zone, the dip switches are not set correctly.  The front AC 
is Zone 1, middle is Zone 2 and rear is Zone 3. 

 

Отзывы: