Setting the Fixed Length Mode 

The number of keys to be buffered and the parity option in the Fixed Length Mode is 

set as follows:  
1.  Press and hold down key '2' for 3 seconds.  The Status LED enters a fast flash 

Mode and emits a long beep. 

2.  Enter a 3 digit number followed by the Hash Key (#).  The first 2 digits specify the 

key buffer length and must be in the range 00 to 11 (eleven).  The third digit must 

be a ‘0’ where there is no parity and ‘1’ where parity is added. 

NOTE: 

If ‘00’ is entered for the key buffer length then the Key Mode reverts to PIN 

Mode. 

3.  On acceptance of the setting, the Status LED changes to Green. 
4.  If the settings are rejected the Status LED changes to Red. 

Single Key 8-bit Burst Mode 

To select this mode, specify the Fixed Length Buffered Mode to be “018”.  This mode 

reports each single key press as 8-bit code.  Use Single Key 8-bit Burst Mode when 

using Multi-discipline Readers in PAC Mode or TAG+PIN Mode. 
 

Key

 

Output

 

11110000 

11100001 

11010010 

11000011 

10110100 

10100101 

10010110 

10000111 

01111000 

01101001 

01011010 

01001011 

Table 2:  Single Key 8-bit Burst Mode 

 
 
 
 
 

Blank Space

 

 

 

Содержание HRK900-0-5-GB Series

Страница 1: ...FARE Tags NOTE HID FeliCa and MIFARE are registered trademarks of HID Global Corporation an ASSA ABLOY Group Brand The Sony Corporation and Koninklijke Phillips Electronics N V respectively Working En...

Страница 2: ...all Indicators on 100 1 2 Wiegand Bus Electrical Interface 0 and 1 Data streams Data Format Tag information 44 bit or 26 bit Wiegand Key information 26 bit Wiegand only Inputs Quantity 4 Type Dry Con...

Страница 3: ...amper HRK900 HRK901 Open Collector Output on Purple Line GND reference on Grey Line NOTE In OEM applications connect the Purple and Grey wires to a Dry Contact Input In Access Portal Systems connectin...

Страница 4: ...amming Pin An Allen Key 2 mm An extra Hexagonal Screw M3 x 8 mm An extra Serial Number Label The Junction Box Reader consists of a Front Cover and a Backing Plate Assembly the Front Cover is attached...

Страница 5: ...face CAUTION You may install Multi discipline Readers in an open environment To do this apply a slanted strip of general purpose black silicone based sealant between the mounting surface and the Backi...

Страница 6: ...015 Page 6 ELECTRICAL CONNECTIONS Connecting the Multi discipline Reader Figure 2 to Figure 7 show typical connections for the Multi discipline Reader Figure 1 Multi Discipline Reader connected to the...

Страница 7: ...MDR300 0 0 GB 08 July 2015 Page 7 Figure 2 Multi discipline Reader Connected to the Impro iTRT...

Страница 8: ...MDR300 0 0 GB 08 July 2015 Page 8 Figure 3 Multi discipline Reader Connected to the IXP20 Controller...

Страница 9: ...MDR300 0 0 GB 08 July 2015 Page 9 Figure 4 Multi discipline Reader Connected to the IXP220 Controller...

Страница 10: ...MDR300 0 0 GB 08 July 2015 Page 10 Figure 5 Multi discipline Reader Connected to the Impro MfT...

Страница 11: ...MDR300 0 0 GB 08 July 2015 Page 11 Figure 6 Multi discipline Reader Connected to the Impro TA or Impro iTA...

Страница 12: ...MDR300 0 0 GB 08 July 2015 Page 12 Figure 7 Multi discipline Reader Connected to the Impro RS or Impro RH...

Страница 13: ...eaders offer four different Output Mode Combinations Select the Output Mode by doing the following 1 On the back of the Multi discipline Reader locate and bridge the two stand alone Pins using the 2 W...

Страница 14: ...e range 00000 to 65535 Wiegand protocol constraints disallow PIN codes from 65536 to 99999 In this case the Status LED turns Red and the Buzzer activates for 2 seconds The Reader can accept 1 to 4 dig...

Страница 15: ...where parity is added NOTE If 00 is entered for the key buffer length then the Key Mode reverts to PIN Mode 3 On acceptance of the setting the Status LED changes to Green 4 If the settings are reject...

Страница 16: ...t The Power on Self test tests the RAM and Flash Checksums If any parameter in the Self test fails the Multi discipline Reader emits a continuous beep for 2 seconds When the Multi discipline Reader pa...

Страница 17: ...2015 Page 17 GUARANTEE OR WARRANTY This product conforms to our Guarantee or Warranty details placed on our Web Site to read further please go to www impro net CE STATUS Models Status MDK901 HRW900 MD...

Страница 18: ...MDR300 0 0 GB 08 July 2015 Page 18 User Notes...

Страница 19: ...MDR300 0 0 GB 08 July 2015 Page 19 User Notes...

Страница 20: ...03 5 0 GB XX HRW902 5 0 GB XX MDR901 5 0 GB XX HRW900 5 0 GB XX MDK900 5 0 GB XX HRW901 5 0 GB XX HRK900 0 5 GB XX HRK901 0 5 GB XX The last two digits of the Impro stock code indicate the issue statu...

Отзывы: