The following troubleshooting guide is intended to address the most common symptoms and is by no means exhaustive. If

symptoms persist, call a qualified service provider. Only a certified electrician should complete electrical work.Turn off all power

to the cooler before attempting to troubleshoot any of the following symptoms.

SYMPTOM

POSSIBLE CAUSES

REMEDY

Unit fails to start or deliver air

1. No electrical power to unit

1. Check power

A. Fuse blown

A. Replace fuse*

B. Circuit breaker tripped

B. Reset breaker*

C. GFCI tripped

C. Reset GFCI*

D. Cord(s) unplugged or damaged

D. Plug in cord(s) or replace if damaged

*

If condition persists, call an electrician

2. Motor overheated (thermally protected)

2. Try to restart after cool down

3. Motor frozen

3. Replace motor

4. Motor able to free spin

4. Replace capacitor

Unit starts but air delivery is inadequate

1. Insufficient air exhaust

1. Open windows or doors

2. Insufficient water – pad not wet

2. Check water distribution system

A. Cooling pads clogged

A. Clean or replace pads

B. Dry streaks on pads

B. Check water level

C. Large dry spots on pads

C. Make sure cooler is level

D. Pump not working

D. Clean or replace pump

E. Loose water connections

E. Check for leaks and correct

Water draining from cooler

1. Float arm improperly adjusted

1. Adjust float to proper level

2. Seat in float valve leaking

2. Replace float valve

3. Drain bushing not tight

3. Tighten fitting

Musty or unpleasant odor

1. Stale or stagnant water in sump

1. Drain, flush and clean sump

2. Pads mildewed or clogged

2. Replace pads

3. Pads not completely wet before

3. Turn on pump before starting fan

cooler is turned on

Knocking, shaking or rattling sounds

1. Loose parts

1. Check and tighten where needed

2. Blower wheel loose or rubbing

2. Inspect and adjust, or replace

Water droplets in the discharged air stream

1. Too much water delivered to the

1. Make sure pads are properly positioned

cooling pads

in the pad frames and that the unit is level.
If necessary, reduce the flow of water to
the pads by tightening the screw on the
hose restrictor clamp found on the pump
discharge hose.

2. Outdoor humidity level is too high

2. Use cooler as a fan only (turn pump off)

or it is raining

or discontinue use of cooler until outdoor

humidity level drops.

TROUBLESHOOTING

NOTE

Do not use cooler cleaners, cooler treatments, or other additives in this evaporative cooler. The use

of any of these products will void your warranty and may impair the life of your evaporative cooler.

!

Содержание Mobile Symphony SPM20

Страница 1: ...tar problemas en su enfriador La falla en seguir estas instrucciones puede da ar y o afectar la operaci n del enfriador y anular la garant a U S Models SPM20 SPM30 SPM45 CAUTION SAVE AND READ THESE IM...

Страница 2: ...Always unplug the electric cord to your cooler before you work on the cooler Your cooler will run on 120 Volt AC 60 Hz cycle current only Plug into three prong grounded GFCI protected electrical rece...

Страница 3: ...ated on level ground Connect to a water supply using a commercial grade garden hose supplied by customer connected to the adapter on the float valve and turn on the water Verify water tight connection...

Страница 4: ...fting the pad frames up and out of the cooler Remove pump from cooler To prevent breakage carefully release the four snap out tabs and lift impeller base plate from the pump body Picture 5 Use a mild...

Страница 5: ...emblies from the unit lift up pull out and then down Lay the metal side down on a flat surface and remove the pad retainers The aspen filters can now be removed Rinse off pad assembly then install new...

Страница 6: ...email customerservice impcollc com Website www impcollc com 5...

Страница 7: ...is level D Pump not working D Clean or replace pump E Loose water connections E Check for leaks and correct Water draining from cooler 1 Float arm improperly adjusted 1 Adjust float to proper level 2...

Страница 8: ...on any exchange e This specific warranty does not cover evaporative coolers installed and operated outside the continental United States III Do not use cooler cleaners cooler treatments or other addi...

Отзывы: