1.16 DUCTING OF FLUES OR 

TECHNICAL SLOTS.

Ducting is an operation through which by the 

introduction of one or more relevant pipes, 

a system is realised for the evacuation of the 

combustion products of a gas appliance made 

up from the coupling of an existing or new 

ducting pipe with a chimney, flue or technical 

slot (also in new buildings) (Fig. 1-30). Ducting 

requires the use of ducts declared to be suitable 

for the purpose by the manufacturer, following 

the installation and user instructions, provided 

by the manufacturer and the requirements of 

the standards.

Immergas ducting system.

 

The Ø60 rigid and 

Ø80 flexible “Green Range” ducting systems must 

only be used for domestic use and with Immergas 

condensing boilers.

In any case, ducting operations must respect 

the provisions contained in the standard and in 

current technical regulations; in particular, the 

declaration of conformity must be compiled at 

the end of work and on commissioning of the 

ducted system. The instructions in the project 

or technical report must likewise be followed, in 

cases provided for by the standard and current 

technical regulations. The system or components 

of the system have a technical life complying with 

current standards, provided that:

- it is used in average atmospheric and 

environmental conditions, according to 

current regulations (absence of combustion 

products, dusts or gases that can alter the 

normal thermophysical or chemical conditions; 

existence of temperatures coming within the 

standard range of daily variation, etc.).

- Installation and maintenance must be 

performed according to the indications 

supplied by the manufacturer and in 

compliance with the provisions in force.

- The max. possible length of the Ø60 flexible 

ducting vertical section is equal to 22 m. This 

length is obtained considering the complete 

Ø80 exhaust terminal, 1m of Ø80 pipe in 

exhaust, two 90° Ø80 bends at boiler outlet.

- The max. possible length of the Ø80 flexible 

ducting vertical section is equal to 30 m. 

This length is obtained considering the 

complete exhaust terminal, 1m of Ø80 pipe 

in exhaust, two 90° Ø80 bends at boiler outlet 

for connecting to the ducting system and two 

direction changes of the flexible tube inside the 

flue/technical slot.

- The max. possible length of the Ø60 flexible 

ducting vertical section is equal to 30 m. This 

length is obtained considering the complete 

Ø80 exhaust terminal, 1m of Ø80 pipe in 

exhaust, two 90° Ø80 bends at boiler outlet.

1.17 CONFIGURATION TYPE B

23

 

OPEN CHAMBER AND FORCED 

DRAUGHT FOR INSIDE.

The appliance can be installed inside buildings in 

B

23

 mode; in this eventuality, all technical rules 

and national and local regulations in force, must 

be complied with.

- Type B open chamber boilers must not be 

installed in places where commercial, artisan 

or industrial activities take place, which use 

products that may develop volatile vapours 

or substances (e.g. acid vapours, glues, paints, 

solvents, combustibles, etc.), as well as dusts 

(e.g. dust deriving from the working of 

wood, coal fines, cement, etc.), which may be 

damaging for the components of the appliance 

and jeopardise functioning.

-  In type B

23

 configuration, the boilers must not 

be installed in bedrooms, bathrooms or in 

bedsitters.

- The installation of appliances in B

23

 

configuration is only recommended outdoors 

(in a partially protected place) or in places that 

are not lived in and which are permanently 

ventilated.

For the installation it is necessary to use the cover 

kit found in paragraph 1.9.

1.18 FLUE EXHAUST TO FLUE/CHIMNEY.

Flue exhaust does not necessarily have to be 

connected to a branched type traditional flue. 

The flue exhaust, for boiler clots installed in C 

configuration, can be connected to a special 

LAS type multiple flue. For B

23

 configurations, 

exhaust is only allowed into individual flue 

or directly into the external atmosphere via a 

relevant terminal. The multiple flues and the 

combined flues must also only be connected to 

type C appliances of the same type (condensing), 

having nominal heat inputs that do not differ by 

more than 30% less with respect to the maximum 

that can be attached and powered by the same 

fuel. The thermo-fluid dynamic features (flue 

flow rate, % of carbon dioxide, % humidity etc...) 

of the appliances attached to the same multiple 

flues or combined flues, must not differ by more 

than 10% with respect to the average boiler 

attached. Multiple and combined flues must be 

specially designed according to the calculation 

method and requirements of the standards, by 

professionally qualified technical staff. Chimney 

or flue sections for connection of the exhaust 

pipe must comply with requisites of technical 

standards in force.

Содержание VICTRIX X12-242I

Страница 1: ...VICTRIX X 12 24 2 I IE Instruction and Warning book 1 036643ENG...

Страница 2: ......

Страница 3: ...user also in the case of transfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and m...

Страница 4: ...ation pump 19 1 25 Kits available on request 20 1 26 Boiler components 21 2 Instructions for use and maintenance 22 2 1 Cleaning and maintenance 22 2 2 General warnings 22 2 3 Control panel 22 2 4 Usi...

Страница 5: ...pliance off immediately and contact a qualified technician e g the Immergas Technical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair...

Страница 6: ...by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percent...

Страница 7: ...ional way using the couplings on the boiler template The boiler safety valve outlet must be connected toadrainingfunnel Otherwise themanufacturer declines any responsibility in case of flooding if the...

Страница 8: ...i e it must be set to On Off mode CARV2 or chrono thermostat On Off electric connection Optional The operations described below must be performed after having removed the voltage from the appliance T...

Страница 9: ...l Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Posit...

Страница 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Страница 11: ...of the straps present in the kit making sure to block the 4 gasket flaps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall...

Страница 12: ...o the external atmosphere The technical regulations in force must be respected Max length of exhaust duct The flue pipe vertical or horizontal can be extended to a max length of 30 straight metres Spa...

Страница 13: ...al intake exhaust kit 80 125 Kit assembly Fig 1 18 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flanged adapter 2 on...

Страница 14: ...l 6 and insert the intake exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3...

Страница 15: ...sent in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using the supplied self...

Страница 16: ...emoval of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flue to...

Страница 17: ...e inside the flue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe...

Страница 18: ...nt the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 21 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion prod...

Страница 19: ...24 CIRCULATION PUMP The Victrix X 12 24 2I series boilers are supplied with a built in circulation pump with 3 position electric speed control The boiler does not operate correctly with the circulatio...

Страница 20: ...rmation of lime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit Relay board on req...

Страница 21: ...ondensation module 11 Flue probe 12 Heat exchanger safety thermofuse 13 Manual air vent valve 14 Sample points air A flue gases F 15 Negative signal pressure point 16 Positive signal pressure point 17...

Страница 22: ...ic hot water temperature selector switch 6 Central heating water temperature selector switch 7 Boiler manometer 8 DHW production phase functioning active 9 Boiler in block does not require release via...

Страница 23: ...ite flame block 20 Return probe anomaly 23 Push button control panel anomaly 24 Block due to flue gas temperature gradient intervention 25 Insufficient circulation 27 Flue probe anomaly 29 Loss of rem...

Страница 24: ...signal loss error occurs 6 times consecutively in 8 5 minutes 38 To eliminate the block the Reset button 3 must be pressed If this phenomenon occurs frequently contact a qualified technician for assis...

Страница 25: ...TI FREEZE PROTECTION The boiler has an anti freeze function that switches on automatically when the temperature fallsbelow 4 C standardprotectiontominimum temperature of 5 C All information relative t...

Страница 26: ...the gas flow rate regulation devices if settings are modified checktheproductionofDHW whentheboiler is connected to an external cylinder unit ensure sealing efficiency of water circuits check ventilat...

Страница 27: ...ed for software updating operations 3 3 TROUBLESHOOTING N B maintenance interventions must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Smell of gas C...

Страница 28: ...eating output ignition power 3 6 ADJUSTMENT OF THE AIR GAS RATIO Important theverificationoperationsoftheCO2 must be carried out with the casing mounted while the gas valve calibration operations must...

Страница 29: ...heating demand of the house Therefore the boiler works normally in a variable gas pressure field between minimum and maximum power depending on the system heat load setting fan speed in rpm hundreds...

Страница 30: ...ich can be configured 0 Off 1 General alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay board contact 5 Heat pump 0 5 0 P5 Relay 3 optional The boiler...

Страница 31: ...every new power supply of the boiler by pressing buttons at the same time 2 and 4 Fig 2 1 for 5 seconds with boiler in stand by N B if the boiler is connected to the CARV2 the stand by function is onl...

Страница 32: ...osen the two screws 4 present in the lower part of the casing front 3 unhook the central fixing 6 exerting slight pressure in the median zone of the side 5 pull the front casing slightly in the lower...

Страница 33: ...sure of 1013 mbar Burner pressure values refer to use of gas at 15 C Victrix X 12 2 I Victrix X 24 2 I METHANE G20 BUTANE G30 PROPANE G31 HEAT OUTPUT HEAT OUTPUT BURNER GAS FLOW RATE BURNER NOZZLES PR...

Страница 34: ...at Nom Q Min mg kWh 48 13 185 20 85 25 Flue temperature at nominal output C 56 63 57 Flue temperature at minimum output C 58 64 59 Victrix X 24 2 I Gas nozzle diameter 8205 gas valve mm 5 80 4 10 4 1...

Страница 35: ...Nom Min 106 9 102 4 106 7 103 0 Efficiency 40 30 Nom Min 107 0 106 8 108 1 107 1 Heat loss at casing with burner On Off 80 60 C 0 89 0 30 0 41 0 50 Heat loss at flue with burner On Off 80 60 C 0 02 2...

Страница 36: ...erial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity dom...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...mergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Cod 1 036643ENG rev ST 000346 000 02 2014 Inglese per IRLANDA...

Отзывы: