M5 menu
(password must be entered)
1
st
Level
2
nd
Level
Options
Description
Default
value
Value
set
by the
technician
SERVICE
P67
P67.1
In winter mode the pump is always powered and so functions
continuously.
P67.2
P67.2
In winter mode the pump is managed by the room thermostat or by the
remote control.
P67.3
In winter mode the pump is managed by the room thermostat or by the
remote control and by the boiler flow probe.
P68
0s ÷ 500s
The boiler is set to ignite the burner immediately after a request for
heating. In the case of particular systems (e.g. area systems with
motorised thermostatic valves etc.) it could be necessary to delay switch-
on.
0 seconds
P69
0s ÷ 255s
The boiler has an electronic timing device that prevents the burner from
igniting too often in the central heating phase.
180 seconds
P70
0s ÷ 840s
The boiler performs an ignition ramp to arrive from minimum power to
nominal heat output.
180 seconds
(3 minutes)
P71
P71.1
OFF domestic hot water “correlated” to the switch-off of the boiler takes
place on the basis of the temperature set using the domestic hot water
adjustment selector switch. Solar function active, if the input domestic
hot water has a sufficient temperature the boiler does not switch on.
P71.2
P71.2
"fixed" domestic hot water OFF; the boiler switches off at 65°C.
Solar function deactivated.
P72
AUTO
OFF
09 L/M
12 L/M
15 L/M
The boiler allows to set the flow rate adjuster on the various levels.
Auto (automatic functioning, therefore with variable flow rate).
Open (adjuster completely open therefore maximum flow rate available).
09 L/M, 12 L/M and 15 L/M (operation with defined flow).
AUTO
RELAY 1
RELE1-0
Relay 1 not used.
RELE1-1
RELE1-1
Heat pump control relay; it switches operation from heating to cooling.
RELE1-2
The relay signals the intervention of a boiler block (Can be coupled to an
external signalling device, not supplied).
RELE1-3
The relay signals that the boiler is in heating or cooling request mode (the
status of the system circulator pump is replicated).
(Can be coupled with an external circulator pump, not supplied).
RELE1-4
Controls the opening of an external gas valve in concomitance with an
ignition request of the boiler burner.
RELE1-5
In the event the boiler circulator pump is replaced with a traditional fixed
speed circulator pump one must connect the new circulator pump to the
relay board.
RELE 2
RELE2-0
Relay 2 not used.
RELE2-0
RELE2-1
In a system divided into zones, relay 2 controls the secondary zone.
RELE2-2
The relay signals the intervention of boiler block (Can be coupled to an
external signalling device, not supplied).
RELE2-3
The relay signals that the boiler is in heating or cooling request mode (the
status of the system circulator pump is replicated).
(Can be coupled with an external circulator pump, not supplied).
RELE2-4
Controls the opening of an external gas valve in conjunction with an ignition
request of the boiler burner.
RELE2-5
Function not available on this boiler model.
RELE2-6
In the event the boiler circulator pump is replaced with a traditional fixed
speed circulator pump one must connect the new circulator pump to the
relay board.