3.2  YEARLY CONTROL AND 

MAINTENANCE OF THE STORAGE 

UNIT.

The following checks and maintenance should 

be performed at least once a year.  

- Visually check for water leaks or oxidation 

from/on connections;

- Check visually that the safety and control 

devices have not been tampered with and in 

particular:

  - adjustment probes;
  - expansion vessel;
  - domestic hot water side safety valve;
- Check integrity of the storage tank sacrificial 

anodes;

- In the case of particularly hard water, decalci-

fication of the storage tank is recommended 

at least once a year. To perform this operation 

the tank must be emptied through the draining 

valve and then remove the flange in order to 

access the inside and use a plastic or wooden 

spatula to remove the most resistant deposits 

and then clean and rinse with a jet of water.

- During the cleaning phase pay particular at-

tention not to damage the internal protection 

of the tank.

3.3  STORAGE UNIT TECHNICAL DATA.

INOXSTOR 200

INOXSTOR 300

INOXSTOR 500

Hydraulic performances

Storage tank unit capacity

l

202,6

279

480,3

Domestic hot water side maximum pressure

bar

8

8

8

DHW side maximum temperature

°C

99

99

99

Maximum coil pressure

bar

6

6

6

Central heating side maximum temperature

°C

90

90

90

Empty storage tank unit weight

kg

60,7

75,0

101,0

Full storage tank unit weight

kg

274,9

366,1

598,9

Heat dispersion

kW h / 24 h

1,95

2,18

2,41

Psbsol

W/K

1,81

2,02

2,23

Upper coil

Exchange surface

m

2

0,72

0,8

1,23

Coil capacity

l

4,1

4,6

7,0

Exchange power

kW

32,0

32,0

32,0

Primary fluid flow rate

l/h

1630

1655

1845

Primary fluid T delta

°C

17

17

14,9

Useful reintegration power

kW

26,3

26,3

26,3

Lower coil

Exchange surface

m

2

1,3

1,31

1,84

Coil capacity

l

7,5

7,5

10,6

Exchange power

kW

52,0

52,0

52,0

Primary fluid flow rate

l/h

2950

3080

3057

Primary fluid T delta

°C

15

14,5

14,6

Useful reintegration power

kW

34,3

34,3

34,3

-  On completion of the operation, re-mount the 

flange by applying the gasket (replace it with a 

new one if it is damaged), close the draining 

valve and fill the tank, checking that there are 

no leaks from the flange or the valve.

Содержание 3.027746

Страница 1: ...Instruction and recommendation booklet IE INOXSTOR 200 300 500 V2 Storage tank 1 041259ENG ...

Страница 2: ......

Страница 3: ...n it is necessary to comply with the provisions specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law Instal lation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructi...

Страница 4: ...unit 7 1 6 Main components 7 1 7 Kit available on request 8 2 User and maintenance instructions 9 2 1 Cleaning and maintenance 9 2 2 Functioning 9 2 3 Emptying the storage tank unit 9 2 4 Case cleaning 9 2 5 Decommissioning 9 3 Control and maintenance 10 3 1 Functional layout 10 3 2 Yearly control and maintenance of the storage unit 11 3 3 Storage unit technical data 11 3 4 Product data sheet in c...

Страница 5: ...ection areas In the event of a malfunction fault or incorrect operation disable the storage tank unit and contact an authorised company e g the Au thorised Technical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Immergas is to comply with the conditions specified in the conventional warranty contract during th...

Страница 6: ...utlet B2 Domestic hot water probe B12 Storage tank solar probe E15 Storage tank integration resistance optional T DHW thermometer X Distance above ground to fix circulation unit Unused DHW side hydraulic connections are to be closed with hydraulic seal caps All connection fittings must be adequately insu lated to minimise heat dispersion Insulated caps to be applied on unused fittings during insta...

Страница 7: ...g and bottom which guarantees a long life The assembly concepts and welding T I G are implemented to the minimum detail to ensure maximum reliability Efficiency the coiled heat exchange surface is sized to supply large quantities of hot water The storage tank has two seats to include the sacrificial anode which is supplied as standard to protect the inner part of the storage tank against corrosion...

Страница 8: ...uest The storage tank unit is set up for application of an integration resistance to provide the anti freeze function which can be calibrated by a specific thermostat Electronic anode kit The storage tank is set up for the installation of the electronic anode Direct current is made to circulate between the device and the tank to be protected via a special titanium anode screwed on and located insi...

Страница 9: ...ween 60 and 65 C because this temperature guarantees the best performance of the storage tank unit and at the same time ensures maximum hygiene maximum affordability delay in lime scale formation The DHW in the storage tank is heated with the passage of CH solar water which circulates inside the coils inside the storage tank unit itself In all cases the maximum temperature inside the storage tank ...

Страница 10: ...ectronic control unit 3 Circulation solar unit 4 Solar system expansion vessel 5 6 bar safety valve 6 System probe and venting unit 7 Mixer valve 8 Storage unit 9 Storage unit thermometer 10 Inspection flange 11 Domestic hot water connection NTC 10 k hom at 25 C supplied as standard 12 Solar panels probe connection AC Domestic hot water outlet AF Domestic cold water inlet MU Storage unit delivery ...

Страница 11: ... TECHNICAL DATA INOXSTOR 200 INOXSTOR 300 INOXSTOR 500 Hydraulic performances Storage tank unit capacity l 202 6 279 480 3 Domestic hot water side maximum pressure bar 8 8 8 DHW side maximum temperature C 99 99 99 Maximum coil pressure bar 6 6 6 Central heating side maximum temperature C 90 90 90 Empty storage tank unit weight kg 60 7 75 0 101 0 Full storage tank unit weight kg 274 9 366 1 598 9 H...

Страница 12: ... F 81W 203L C INOXSTOR 200 V2 100W 480L C INOXSTOR 500 V2 91W 279L C INOXSTOR 300 V2 INOXSTOR 200 V2 INOXSTOR 500 V2 INOXSTOR 300 V2 A 2017 812 2013 A A B C D E F INSTALLER USER MAINTENANCE TECHNICIAN 3 4 PRODUCT DATA SHEET IN COMPLIANCE WITH REGULATION 812 2013 ...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 041259ENG rev ST 003315 000 09 17 Inglese per IRLANDA IE ...

Отзывы: