Domestic hot water level.
This section includes all the necessary parameters for programming the domestic hot water circuit.
PARAmETER
Description
Regulation
Setting range / Parameters
D. H. W.
NIGHT
Reduced temperature for domestic hot water
40 °C
5 °C ... Domestic hot water temperature
ANTILEGIO-
NELLA
DAY
D.h.w. legionella protection function (day)
OFF
OFF
No Legionella protection function
Mo...Su
Legionella protection in the selected day
All
Legionella protection each day of the week
03
D.h.w. legionella protection function (time)
02:00
00:00...23:50
04
Legionella protection (temperature)
60 °C
10 °C ... D.h.w. maximum temperature
05
D.h.w. temperature sensor type
1
1
D.h.w. temperature sensor
2
D.h.w. thermostat
06
D. h. w. maximum temperature
60 °C
20 °C ... maximum heat generator temperature
07
D. h. w. functioning mode
2
1
Parallel functioning
2
Prioritary functioning
3
Conditioned prioritary functioning
4
Parallel functioning depending on climatic conditions
5
Prioritary functioning with intermediate heating
6
Prioritary separated activation
7
External functioning
08
Storage tank anti-drain function
OFF
OFF
- disactivated
ON
- activated
09
D.h.w./delivery temperatures ∆T
20 K
0 ... 50 K;