EN
TEMP V4 IP68 Sigfox RC1 - Guide utilisateur / User guide version V3.1.1
55 of 57
FR
CAUTION: To maintain the IP 68 it is important to screw the cable glands fully and screw the screws with a PZ.1 head
and a tightening torque of 0.9 N.m.
As a reminder the probe 1 is on the rounded side of the housing, the probe 2 is on the flat side of the housing.
Remove the
screws
1
2
1
Open the product by
pulling on the cable
gland
WARNING : do not
pull on the wires
2
2
1
5V + -
1 2 3 4
Insert the cable of the probe supplied with
the product and connect the wires to the
terminal blocks:
• for
probe 1*
terminals 3 and 4
• for
probe 2*
terminals 1 and 2
3
Remove the gland plug
4
5V + -
1 2 3 4
5V + -
1 2 3 4
5.2. Wiring a probe
In order to wire a probe, please follow these instructions:
*The wiring of the probes at the right place is important to match the associated registers and for the interpretation of the results (cf. Technical
Reference Manual, Registers).
www.ime.de