D
x
Telemetry System
Manual Vers. 2.7
18
/
92
3
Quickstart
3.1
Connect the D
X
RCI
Connect the D
X
RCI to a power source. Therefore, use the DC-Inputs (9-36V DC) or
connect the included power cable to the mains voltage.
To configure the D
X
via PC, connect the PC and D
X
with the included Ethernet cable.
For data transmission via CAN-Bus, connect a CAN cable (CAN1: CAN-Output;
CAN2: CAN-Input)
Please note:
The D
X
has no built-in CAN terminating resistor. In case the D
X
is
placed at the end point of a CAN bus chain, you
have to
place a 120
Ω termination
resistor between connector and CAN jack.
Plug BNC cables to the analog outputs of the RCI to tap measurement data. Analog
outputs are freely programmable to all data channels (for configuration, see section
3.8).
3.2
Connect the D
X
SCT
Connect the D
X
SCT to a power source. The SCT can either be supplied by
battery/rechargeable battery or inductively by a ring or fix stator. As soon as supplied with
power, the SCT is transmitting measurement data. Please refer to Section 2.2 for more
information on power input connection.
Note:
To check whether voltage application to drive the SCT is sufficient, measure the strain
gauge supply voltage (see section 2.2). Its voltage level is 4.096 ± 0.1 V when the device is
sufficiently supplied.
3.3
Turn the D
X
RCI on and off
To turn the D
X
RCI on or off, press the button in the center of the scroll wheel for about 5
seconds.
3.4
Configure the D
X
with a PC
With this function, configuration can be done conveniently with your PC instead of using the
scroll wheel.
To configure the D
x
using a Web browser, a local network connection between D
x
and
measuring computer must be set up. Connect the Ethernet interface of the D
x
to your
computer with an Ethernet cable.
Please note:
Your computer must be assigned with an IP address (IPv4 protocol) from the
same network segment (i.e, the first three digits has to match with the D
X
IP address).
Factory setting of the D
x
IP-address is 192.168.000.212.
In this case, assign for example the IP address 192.168.000.100 to your computer.
Furthermore, deactivate your computer’s dynamic address assignment (DHCP).
Содержание CAEMAX DX
Страница 31: ...Dx Telemetry System Manual Vers 2 7 31 92 Figure 20 Strain gauge channel configuration...
Страница 44: ...Dx Telemetry System Manual Vers 2 7 44 92 Menu tree continued...
Страница 84: ...Dx Telemetry System Manual Vers 2 7 84 92 10 Questions Answers 10 1 Inductive Power Supply Troubleshooting...
Страница 85: ...Dx Telemetry System Manual Vers 2 7 85 92...
Страница 86: ...Dx Telemetry System Manual Vers 2 7 86 92...