Heat Recovery Unit ILOX 129 - Installation, Operation and Maintenance
FläktGroup DC_10201GB_20190207_R2
We reserve the right to make changes without prior notice
PARAMETER LIST
Parameter
Type of value
1)
Range
Unit
Standard value Comment
7.4 Contact functions
DI1 Timer input 1
R/W
NO/NC
–
NO
DI2 Timer input 2
R/W
NO/NC
–
NO
DI3 Rotation monitor
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI4 Pressure monitor
defrosting
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI5 Fan / Filter monitor
TF
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI6 Fan / Filter monitor
FF
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI8 Fire alarm
R/W
NO/NC
–
NO
External function, should be changed to NC during use
DI9 Cooker hood con-
nector
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI7 Alarm heating
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
DI10 Alarm cooling
R/W
NO/NC
–
NO
Not applicable to domestic ventilation
8. Configuration
8.1 IP address
R/W
Static / Dynamic
–
Dynamic
Static = Manual setting
Dynamic = Automatic assignment of IP address via DHCP
IP address
R/W
–
–
–
Subnet mask
R/W
–
–
–
8.2 Menu config.
Log to USB
R/W
Yes / No
–
No
Only for troubleshooting
Unit type
R
–
–
Domestic
Auto logout time
R/W
0-32767
min
10
Threshold value heating
R/W
0-100
%
0
For installation engineers and
service personnel
Threshold value cooling
R/W
0-100
%
0
For installation engineers and
service personnel
Threshold value recovery
R/W
0-100
%
0
For installation engineers and
service personnel
Threshold value external
fan
R/W
0-100
%
5
For installation engineers and
service personnel
8.3 Screen saver
Screen saver
R/W
On / Off
–
On
Time
R/W
–
min
10
8.4 Modbus
Modbus slave address
BMS
R/W
0-255
–
2
Baud rate
R/W
9.6, 19.2, 38.4
–
19.2
Parity
R/W
no parity, even, odd
–
None
Data bit
R/W
7.8
–
8
Stop bit
R/W
1.2
–
1
8.5 Mac address
Mac address
R
–
–
–
8.7 Password
Automatic logout
R/W
Yes / No
–
Yes
Password 1
R/W
–
–
–
Used to change the password
8.8 Om
Software HMI
–
–
–
Software control card
R
–
–
–
Bootloader version
R
–
–
–
1)
R/W = Read and write value, R = Read only value