26
Heat Recovery Unit ILOX 129 - Installation, Operation and Maintenance
FläktGroup DC_10201GB_20190207_R2
We reserve the right to make changes without prior notice
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
6. Air quality
–
–
–
–
Not applicable to the ILOX unit
7. Alarm management
7.1 Alarm settings
Filter alarm time
R/W
0-600
days
180
Set to 0 to deactivate filter alarm
Summation alarm output A+B
R/W
Yes / No
–
Yes
Activate temperature alarm
R/W
Yes / No
–
Yes
Temperature alarm
R/W
-10–+10
°C
5
Activate rotor belt test
R/W
Yes / No
–
No
Not applicable to the ILOX unit
Tacho signal alarm
R/W
Yes / No
–
Yes
7.2 Alarm categories
Fire alarm
R/W
A/B
–
A
External function
Sensor error supply air
R/W
A/B
–
A
Sensor error outdoor air
R/W
A/B
–
A
Sensor error extract air
R/W
A/B
–
A
Sensor error frost protection
R/W
A/B
–
B
Not applicable to domestic ventilation
Sensor error defrosting
R/W
A/B
–
B
Not applicable to domestic ventilation
Sensor error AI10
R/W
A/B
–
B
Not applicable to domestic ventilation
Filter alarm
R/W
A/B
–
B
Fan monitor, supply air
R/W
A/B
–
B
Not applicable to domestic ventilation
Fan monitor, extract air
R/W
A/B
–
B
Not applicable to domestic ventilation
Pressure monitor heat ex-
changer
R/W
A/B
–
B
Not applicable to domestic ventilation
Rotor monitor
R/W
A/B
–
A
Not applicable to domestic ventilation
Filter monitor, supply air
R/W
A/B
–
B
Not applicable to domestic ventilation
Filter monitor, extract air
R/W
A/B
–
B
Not applicable to domestic ventilation
Overheating electric heater
R/W
A/B
–
B
Not applicable to domestic ventilation
Circ. pump heating
R/W
A/B
–
B
Not applicable to domestic ventilation
Frost protection
R/W
A/B
–
B
Only for water heating
Summation alarm cooling
R/W
A/B
–
B
Not applicable to domestic ventilation
Circ. pump cooling
R/W
A/B
–
B
Not applicable to domestic ventilation
Temperature alarm
R/W
A/B
–
A
Rotor belt alarm
R/W
A/B
–
A
Not applicable to the ILOX unit
7.3 Alarm delays
Fire alarm
R/W
0-9999
s
2
External function
Sensor error supply air
R/W
0-9999
s
5
Sensor error outdoor air
R/W
0-9999
s
5
Sensor error extract air
R/W
0-9999
s
5
Sensor error frost protection
R/W
0-9999
s
5
Only for water heating
Sensor error defrosting
R/W
0-9999
s
5
Only for water heating
Sensor error AI10
R/W
0-9999
s
5
Not applicable to domestic ventilation
Fan monitor, supply air
R/W
0-9999
s
120
Not applicable to domestic ventilation
Fan monitor, extract air
R/W
0-9999
s
120
Not applicable to domestic ventilation
Rotor monitor
R/W
0-9999
s
2
Not applicable to domestic ventilation
Filter monitor, supply air
R/W
0-9999
s
60
Not applicable to domestic ventilation
Filter monitor, extract air
R/W
0-9999
s
60
Not applicable to domestic ventilation
Overheating electric heater
R/W
0-9999
s
2
Not applicable to domestic ventilation
Circ. pump heating
R/W
0-9999
s
2
Not applicable to domestic ventilation
Frost protection
R/W
0-9999
s
2
Only for water heating
Summation alarm cooling
R/W
0-9999
s
2
Not applicable to domestic ventilation
Circ. pump cooling
R/W
0-9999
s
2
Not applicable to domestic ventilation
Temperature alarm
R/W
0-9999
min
10
Rotor belt alarm
R/W
0-9999
s
60
Not applicable to the ILOX unit
PARAMETER LIST
1)
R/W = Read and write value, R = Read only value