ONLINE ELECTRONICS LTD
ID5002P MANUAL RevA01
Page 21 of 21
10.
As part of a routine maintenance schedule, the condition of the window cement shall be
periodically inspected for any degradation or discolouration of the cement that may
compromise the explosion protection.
11.
As per IEC/EN 60079-14 the ID5002P shall be either isolated from earth or connected at
one point to the equipotential bonding system.
12.
If enclosure equipotential bonding or earthing is connected then to avoid double earth
faults the EXTSW connection must not be connected to a second earth.
PARAMETER TABLES:
The ID5002P must be connected via suitably certified intrinsically safe barriers satisfying the
following parameters unless otherwise stated:
Description Power
Supply
RS485
4-20mA
Current
Loop
Internal
Switch
External
Switch
Remote
Switch
Sensor
Terminals
VIN
0V
RS485+
RS485-
RS485GND
CL+
CL-
INTSW
0V
EXTSW
0V
TRIG+
TRIG-
SEN+
SEN-
Ui
21.5V
6.0V
29.4V
-
NOTE1
0V
29.4V
-
Ii
604mA
600mA
125mA
-
NOTE1
0mA
125mA -
Pi
3243mW 450mW
920mW
-
NOTE1
0W
650mW -
Ci (int)
0μF
110nF
121nF
-
NOTE1
0μF
0μF
-
Li (int)
0μH
0μH
0μH
-
NOTE1
0μH
0μH
-
Uo
-
-
-
-
NOTE1
4.1V
-
23.1V
Io
-
-
-
-
NOTE1
5mA
-
28mA
Po
-
-
-
-
NOTE1
5mW
-
160mW
Co (ext)
-
-
-
-
NOTE1
10uF
-
1.02μF
Lo (ext)
-
-
-
-
NOTE1
0.2H
-
0.19H
Example
Accessory
NOTE3
GM
PSD5201
MTL
7755ac
MTL
7787+
NA
NOTE1
GM
D1044S
MTL
7787+
NA
NOTE2
Description Relay
Terminals
NO1
COM1
NC1
NO2
COM2
NC2
Ui
15.0V
OR
21.6V
OR
24.0V
OR
30.0V
OR
45.0V
Ii
2000mA
611mA
433mA
253mA
113mA
Pi
7500mW
3299mW
2958mW
1897mW
1271mW
Ci
0μF
0μF
0μF
0μF
0μF
Li
0μH
0μH
0μH
0μH
0μH
Example
Barrier
NOTE4
MTL
7758+
MTL
7715P+
MTL
7715P+
MTL
7787P+
MTL
7787+
NOTE1 The ID5002P is supplied with a suitable internal switch.
NOTE2 The ID5002P is supplied with a suitable sensor.
NOTE3 Use only barriers or accessories supplied or approved by Online Electronics Ltd.