FUNCTIONAL DESCRIPTION
Note: All function adjustments will be auto
-
matically accepted 15-seconds after pressing
a given touch zone or button. The user may
press the MODE/SET button to immediately
accept the adjustment manually.
CHANNEL SELECTION
This control may be operated in 3 different
sub-channels for applications where 2.4GHz
interference causes delayed operation of the
remote control. The factory default is Channel
3. To change the channel on the transmitter:
•
Touch the CHANNEL PROGRAM and
CHANNEL UNLOCK zones simultane
-
ously and hold for 5-seconds.
•
The LCD screen will go blank except
“Ch” will be displayed in the SET TEMP
Zone and either “01”, “02”, or “03” will
be displayed in the ROOM TEMP Zone.
•
Press the UP or DOWN buttons to
change the channel number (01-03).
•
Press the MODE/SET Button to return to
the normal operating display.
Receiver Operation Notes:
•
The receiver manufacturer may refer to
channels 01, 02, or 03.
•
Receiver must be paired with transmitter
in the receiver’s factory default channel.
•
Once paired, the channel selection may
be changed in the transmitter per the
instructions above.
•
Once the channel selection is changed in
the transmitter, the power supply to the
receiver must be removed for at least
30-seconds, then re-applied.
•
The receiver will recognize the new
channel selection after about 30-sec-
onds to 1-minute and normal operation
will resume.
MODES OF OPERATION
OPERATION MODES:
•
MANUAL OFF
•
MANUAL ON
•
THERMOSTAT (with optional PRO
-
GRAM Mode)
The modes may be cycled in the order above
by touching the MODE Zone or pressing the
MODE/SET Button.
MANUAL OFF MODE:
•
Transmits flame OFF command.
•
Pilot Method: Intermittent Pilot Ignition
(IPI)/Spark-to-Pilot only (continuous/
standing pilot not allowed)
•
Pilot flame will be turned OFF
•
LCD Displays:
•
MODE Zone: OFF is displayed
•
ROOM TEMP Zone: Measured tempera-
ture is displayed
•
SET TEMP Zone: Blank
•
TIME/PROG Zone: Current day indicator
and current time is displayed
•
FLAME Zone: Blank
MANUAL ON MODE:
•
Transmits flame ON command.
•
Pilot Method: Intermittent Pilot Ignition
(IPI)/Spark-to-Pilot only (continuous/
standing pilot not allowed)
•
Pilot flame will be ignited before turn
Main Flame ON.
•
LCD Displays:
•
MODE Zone: ON is displayed
•
ROOM TEMP Zone: Measured tempera-
ture is displayed
•
SET TEMP Zone: Blank
•
TIME/PROG Zone: Current day indicator
and current time is displayed
•
FLAME Zone: A Flame Icon and flame
setting level number is displayed
THERMOSTAT MODE:
•
Will cycle flame on and off based on
room and set temperatures. Will transmit
ON command if SET TEMP (+SWING)
is higher than ROOM TEMP and will
transmit OFF command if SET TEMP
(-SWING) is lower than ROOM TEMP.
•
Built-in thermostat will measure room
temperature.
•
All programming should be written for
deg. F and converted to deg. C when
selected.
•
Temperatures may be displayed in
degrees F (factory default) or degrees
C. Press the UP and DOWN Buttons
simultaneously to change between
degrees F and C.
•
SET TEMP: While in THERMOSTAT
mode, press the UP or DOWN Button