10
3. Principle picture
4. System description
4.1 Application
The TDS controller with limiting function FARB2 is used for continuous monitoring of the conductivity
of liquids.
The conductivity is measured with a measuring cell. This consists of a special conductivity probe and
the container wall or protective tube.
The conductivity is displayed via a 4*7 segment display and an active 4..20mA output interface. A
relay (SPDT) is provided for limiting or switching functions.
The requirements of EU Directive 2014/68/EU, the standards EN 13445, EN 12952-11 and
EN12953-9, EN 61010-1, EN 61326-1 are taken into account.
Probes for use with the FARB2:
Name
PS
TS
Connection
Special feature
EL18
32 bar
239°C
G ½"
Pipeline with flange mounting
EL22
32 bar
239°C
G ½"
Optionally installation with T-piece
EL23
80 bar
296°C
G ½"
Protection tube installation
FARB2
Level probe EL 22
TDS Control valve with:
- Positioner
- Motor control open/close
TDS probe EL 22