background image

 

 

15 

8.  Electrical connection 

Only  skilled  and  qualified  personnel  may  carry  out  the  electrical 
connection according to the wiring diagram! 

Respect the instructions of the VDE (Association for Electrical, Electronic 
& Information Technologies) and of the local network operators for the 
installation to be provided by the customer! 

Only use cables that are suitable for the operating range! 

Observe  the  switching  time  of  the  magnetic  switch  when  designing  a 
safety circuit. Adhere to basic and reliable safety principles as per  
DIN EN ISO 13849 for electrical components. 

 
 

8.1  Wiring diagram 

 
 
 
 
 
 

 

 

Connection wires: 

 

brown 

yellow 

 
 
 
 
 
 

white 

green 

 

 
 
 
 
 
 
 
 
 
 
 

Identification arrow 

 
 
We recommend to use customary RC combinations or a suitable varistor  
(e.g. 0,1 μF/100Ω) as inductive consumer to extend the contact life of the magnetic switch. 
Resistance value (Ω) and power rating (W) depend on customer indications. 
 
We suggest to use silicon cables free of acetic acid for the further connection cable in the 
area „connecting housing inside“. 
 

 

 

Caution 

Содержание BA14

Страница 1: ...Edition 11 2020 D 07 B 50203 EN 00 ASSEMBLY and OPERATING MANUAL BA14 RBA24 RBA34 Water level controller and limiter...

Страница 2: ...e Steam is our passion and we offer you the entire programme for the safe and economic operation of your plants especially in the steam and condensate sector Please read the installation and operating...

Страница 3: ...ons for this device 9 1 5 Exclusion of liability 9 2 Contents of packing 9 3 Important information 10 3 1 Intended use 10 4 Explanations 10 4 1 System description 10 4 2 Function 10 5 Technical data 1...

Страница 4: ...cal data magnetic switch 16 8 4 Insulation of electrical components 16 9 Commissioning 17 9 1 Commissioning of unit together with the boiler 17 9 2 Commissioning of unit if boiler is already in operat...

Страница 5: ...5 Table of Contents cont 12 Drain valve 21 12 1 Construction 21 12 2 Assembly 22 13 Spare parts 25 14 Decommissioning 26 15 Declaration of Conformity 27...

Страница 6: ...bove tasks IGEMA GmbH accepts no liability for damage to property or personal injury caused by unqualified persons or by failure to observe these installation and operating instructions If no sufficie...

Страница 7: ...s The maximum values of the pressure and temperature range of the device must be checked before installation If the maximum allowable operating values of the device are lower than those of the system...

Страница 8: ...been depressurised and that the pressure has been safely reduced to atmospheric pressure In principle no system should be regarded as unpressurized even if indicated by pressure measuring devices suc...

Страница 9: ...the applicable safety and environmental laws according to GGVSEB German ordinance on the national and international carriage of dangerous goods by road rail and inland waterways must always be observ...

Страница 10: ...53 AD 2000 or ASME Boiler Type EC type examination registration number BA14 Z D 002 10439 14 Rev 2 RBA24 34 Z D 002 10440 14 Rev 2 4 Explanations 4 1 System description The float switch different vers...

Страница 11: ...nge of adjustment W mm BA 14 40 RBA 24 100 150 RBA 34 250 350 450 550 650 750 Dimensions A Z Type Dim Z mm Dim mm A1 A2 BA14 RBA24 A D 550 PS bar 32 80 32 80 RBA34 IP54 A D 550 BA14 RBA24 34 112 152 1...

Страница 12: ...limits 5 5 Corrosion resistance The safety of the unit is not influenced by corrosion if it is used as intended 5 6 Identification plate Marking The following data are indicated on the identification...

Страница 13: ...witch 3 Transmitter magnet 4 Transmitter tube 5 Thread bolt 6 Hex nut 7 Upper part 8 Sealing ring 9 Transmitter tube cap 10 Retaining spring 11 Float rod 12 Float 13 Standpipe 14 Drain valve 15 Drain...

Страница 14: ...sport protection Ensure that sealing surfaces are clean and undamaged Use sealing material as per EN1514 and screws as per DIN2510 or DIN974 material 1 7709 Mount float switch 7 2 Version with welding...

Страница 15: ...hing time of the magnetic switch when designing a safety circuit Adhere to basic and reliable safety principles as per DIN EN ISO 13849 for electrical components 8 1 Wiring diagram Connection wires br...

Страница 16: ...1 maker Connection wire 1 x 0 5 mm 16 x 0 2 Cu tinned PTFE Wire length L 200 mm Max perm temperature 70 C bis 260 C Type Switching voltage U Switching current I Max power UxI M130 K 250 VAC 1 A 150 V...

Страница 17: ...gnetic switch 2 in operating condition and adjust the height if necessary The magnetic switch 2 must be correspondingly affixed onto the transmitter tube 4 9 2 Commissioning of unit if boiler is alrea...

Страница 18: ...drain valve 14 Slightly open shutoff valves W D standpipe is filled now Fully open shutoff valves W D after the standpipe is filled 10 2 Function test A function test is prescribed for float switches...

Страница 19: ...il the unit has cooled Close valves W D see sketch chapter 5 Open drain valve 14 and drain unit Caution during disassembly Residual medium may escape and further evaporation is possible Unfasten bolti...

Страница 20: ...eplace deformed or corroded parts Insert complete float device 11 12 into transmitter tube 4 Place transmitter tube cap 9 on transmitter tube 4 and secure with retaining spring 10 Close standpipe see...

Страница 21: ...connection 12 as per DIN 2353 DS12 With limit switch to register the blow down process Other drain connections on request 1 Valve housing 11 Handwheel 2 Sealing ring 12 Plate OPEN CLOSED 3 Seat 13 Cap...

Страница 22: ...12 3 Commissioning Rust sand or similar impurities inside of the medium or during first flushing can cause leakage if they remain in the area of the seat Purging of valve Fully open valve for purging...

Страница 23: ...tighten with tightening torque Md 220 Nm Place handwheel 11 and tighten cap nut 13 Replacement of complete upper part For dismounting of component parts see Replacement of packing Unscrew seat 3 with...

Страница 24: ...e drain valve Quick action contact of limit switch must react after approx 2 turns of the handwheel open valve Contact position 13 14 breaker changes to 21 22 maker see fig contact position Readjustme...

Страница 25: ...olt 50 1 40 00381 4 8 Sealing 40 00189 1 6 Hex nut 40 00723 8 5 Bolt 80 40 00414 8 8 Serrated gasket 40 00200 1 6 Hex nut 40 00737 16 1 Version square flange 13 2 Drain valve Pos No Designation Articl...

Страница 26: ...it and separate waste products When disposing the unit observe legal regulations for waste disposal This high quality IGEMA product was designed manufactured and tested with the application of the QM...

Страница 27: ...27 15 Declaration of Conformity...

Страница 28: ...28 Antwerpener Str 1 Fon 49 2501 92424 0 48163 M nster Fax 49 2501 92424 99 Deutschland info igema com www igema com IGEMA GmbH...

Отзывы: