Auto Setup Table 1

Relay 1 and Relay 2 on the TOC-625-Micro are set to be normally energised, de-energising on alarm or 
power failure.

The TOC-625-Micro can FIND up to 10 devices. These can be any mix of gas detectors and up to 2 output 
nodes

The TOC-625-Micro can FIND up to 4 addressable relays on 2 output nodes. Relay nodes supplied with 
TOC-625-Micro need to be addressed as follows and will operate according to the following table. 

Node Relay Address

Relay 1  Relay 2
              Mutable
4201      4202

Relay 1  Relay 2
              Mutable
4203      4204

Output Node 1

Output Node 2

Relays Active on
First Alarm

Note that mutable relays re-energise on second alarm.

       Use the Setup Wizard at Startup

       TOC-625-MCP Automatically Finds Connected Devices

       Detected Devices are Automatically Installed

       Alarm Levels and Outputs are Automatically Set

TOC-625 MICRO SERIES

GAS DETECTION SYSTEM

International Gas Detectors

The control panel should be located outside the 
area where the detectors are located so that it is 
not necessary to enter to the area with a gas alarm 
to reset or check the controller.

For detector locations refer to IGD document 
BS023 Siting Gas Detectors. This is available from 
the downloads area of our website.

Detectors are supplied pre-calibrated. If it is 
required to check or demonstrate operation, test 
gas kits are available from IGD

Note Alarms Levels and Types Are Fixed and Cannot be Adjusted

TOC-625-MCP is a multi-channel detector controller in an easily installed and implemented small 

format package using pre-made plug and socket cables. The system can be used with the Tocsin 

Addressable range of detectors or I/O modules listed in the auto setup table. The use of pre-made 

cables  means  there  is  very  little  installation  required,  reducing  cost  and  enhancing  safety.625 

Micro has a unique Auto Setup Function. 

OLIVER

IGD

Triton House

Tel: +44 (0)161 483 1415

CO

H S

2

CO

2

SO2

NO

NO

2

CH4

International Gas Detectors

Crosby St
Stockport
SK2 6SH
England

Fax: +44 (0) 161 484 2345

Email: [email protected]

Website: www.internationalgasdetectors.com

Ref T625M-3

Flammables
Carbon Monoxide
Carbon Dioxide
Carbon Dioxide
Chlorine
Oxygen

Type
Rising - Latching
Rising - Latching
Rising - Latching
Rising - Latching
Rising - Latching
Falling - Latching

Range
0-100% LEL
0-100ppm
0-5000ppm
0-5%
0-5ppm
0-25%

Alarm 1 / Relay 1
10% LEL
30ppm
1500ppm
0.5%
0.5ppm
19.5%

Alarm 2 / Relay 2
20% LEL
75ppm
5000ppm
1.5%
1ppm
18.5%

Gas

Outputs

Hydrogen Sulphide 0-50ppm

Rising - Latching

5ppm

10ppm