Ultrasonic flow meter
SU2020 SU2021 SU2621 SU8020 SU8021 SU8621 SU9020 SU9021
35
10.3.6.2 Parameter setting via IO-Link: error behaviour of the outputs
u
Call up [Parameters] > [Output Configuration].
u
Select [FOUx] and set the error behaviour for OUTx: [On], [OFF], [OU].
10.3.7 Output off
The output signal can be deactivated. The output then goes to high impedance.
Communication via the IO-Link interface on OUT1 remains active.
10.3.7.1 Parameter setting via unit keys: output off
u
Go to the [EF] > [OUTx] menu.
u
Select [SELx] and set [OFF].
10.3.7.2 Parameter setting via IO-Link: output off
u
Call up [Parameters] > [Output Configuration].
u
Select [oux] and set [OFF].
10.4 Application configuration
The chapter describes the setting options for adaptation to your specific application.
10.4.1 Guided installation
An installation wizard can be used for fast and easy parameter setting of the unit. On-screen
instructions guide users through the entire parameter setting process.
Guided installation via an installation wizard (
.
10.4.1.1 Parameter setting via unit keys: guided installation
u
Call up the menu [EF] > [CFG].
u
Select [Guide] and set [Yes].
10.4.2 Standard unit of measurement
A unit of measurement can be selected with which the process value is shown in the display by
default. All further parameter settings are based on this unit.
Selectable values:
•
Volumetric flow:
– SUxxx0: l/min; l/h; m
3
/h; m/s.
– SUxxx1: l/min; l/h; m
3
/h; m/s; gal/min; gal/h; ft/s.
•
Temperature:
– SUxxx0: °C
– SUxxx1: °C or °F
10.4.2.1 Parameter setting via unit keys: Standard unit of measurement
u
Call up the menu [EF] > [CFG].