4.3 Analogue function
• The unit provides an analogue signal that is proportional to the volumetric flow
quantity and the medium temperature�
• Within the measuring range the analogue signal is 4���20 mA�
• If the measured value is outside the measuring range or in the event of an
internal error, the current signals indicated in Figure 1 are provided�
• The measuring range is scalable:
[ASP] determines at which measured value the output signal is 4 mA�
[AEP] determines at which measured value the output signal is 20 mA�
Minimum distance between [ASP] and [AEP] = 20 % of the final value of
the measuring range�
MAW
Initial value of the measuring range
For non-scaled measuring range
(= factory setting)
MEW
Final value of the measuring range
ASP
Analogue start point
For scaled measuring range
AEP
Analogue end point
Table 1: Definitions