9 Set-up
After power on and expiry of the power-on delay time of approx� 5 s the unit is in
the RUN mode (= normal operating mode)� It carries out its measurement and
evaluation functions and generates output signals according to the set parame-
ters�
During the power-on delay time the output signal is at 20 mA�
10 Parameter setting
Parameters can be set before installation or during operation�
If you change parameters during operation, this will influence the function�
►
Ensure that there will be no malfunctions in your plant�
During parameter setting the unit remains in the operating mode� It continues to
monitor with the existing parameter until the parameter setting has been complet-
ed�
CAUTION
If the medium temperature is above 50 °C (122 °F) parts of the housing can
increase in temperature to over 65 °C (149 °F)�
> Risk of burns�
►
Do not touch the device with your hands�
►
Use another object (e�g� a ballpoint pen) to carry out settings on the unit�