8
MAW
Initial value of the measuring range
For non-scaled measuring range
(= factory setting)
MEW
Final value of the measuring range
ASP
Analogue start point
For scaled measuring range
AEP
Analogue end point
Table 1: Definitions
MEW
MAW
AEP
ASP
-120
Q
[% MEW]
[°C]
T
-40
-20
80
100 110
-130
-50
[°F]
-40
-4
176
212 230
-58
120
100
0
130
4
3,5
FOU=OFF
20
21,5
22
[mA]
FOU=On
1
2
5
4
6
5*
6*
3
cr.UL UL
OL cr.OL
Figure 1: Characteristics of the analogue output according to the standard IEC 60947-5-7�
Q:
Flow (a negative flow value means flow against the marked flow direction)
T:
Temperature
UL:
Below the display range
OL:
Above the display range
cr�UL:
Below the detection zone (error)
cr�OL:
Above the detection zone (error)
FOU=On: Default setting at which the analogue signal goes to the upper final value in
case of an error�*
FOU=OFF: Default setting at which the analogue signal goes to the lower final value in
case of an error�*
* The type of error is displayed: cr�UL, cr�OL, Err (→ 12)�