SI5012
Flow monitor
12
8 Set-up
u
Switch on the supply voltage.
w
All LEDs light and go out again step by step. During this time, the output is closed if set to
normally open and open if set to normally closed.
w
The device is in the operating mode.
u
Let the normal flow circulate in the installation.
u
Check the display and determine further actions:
Display
Explanation
1
The factory setting is suitable for the application.
No further settings are required.
2
Your normal flow is below the representation range of the display.
2 setting options:
u
u
3
Your normal flow exceeds the representation range of the display (LED 9 flashes).
u
Tab. 1: Display for factory setting (normally open function, switch point at LED 7)
LED orange: output closed; LED red: output open
The factory settings can be restored at any time.
For media other than water:
u
Carry out additional adjustment to the minimum flow: Low-flow adjustment (
13).