8
6 Set-up and settings for water
(For media other than water → 7.1: Low flow adjustment).
►
Switch on the supply voltage�
>
All LEDs light and go out again step by step. The unit is in the operating mode.
►
Let the normal flow circulate in the installation�
► Check the display and determine further actions.
1
The factory setting is suitable for the applica-
tion�
►
No further settings are required�
2
Your normal flow is below the representation
range of the display�
► Carry out high flow adjustment (→ 6.1).
3
Your normal flow exceeds the representation
range of the display (LED 9 flashes).
► Carry out high flow adjustment (→ 6.1).
You can restore the factory setting any time. (→ 7.2).
6.1 High flow adjustment (optional)
The unit determines the existing flow as normal flow and adapts the display repre-
sentation (all LEDs light green).
Proceed as follows:
►
Let the normal flow circulate in the installation�
►
Press the pushbutton and keep it pressed�
>
LED 9 lights, after approx. 5 s it flashes.
►
Release the pushbutton�
The unit is now adapted to your flow conditions� It passes into the operating mode,
the display should now show example 1�