IFM SI0551 Скачать руководство пользователя страница 10

10

8 Error during adjustment

If no adjustment is possible, all LEDs flash red. The unit then passes into the 

operating mode with unchanged values�

Possible cause /aid:

Error during installation�

 

Read chapter 3 Installation� 

Check whether all requirements have 

been met�

The difference between maximum flow and 

minimum flow is too small�

 

Increase the flow difference and carry 

out the adjustment once again�

The sequence high flow /low flow adjust-

ment was not adhered to�

 

► Carry out the two adjustment operations 

again in the right sequence�

9 Operation

After every power on all LEDs light and go out again step by step (during this time 

the output signal is 20 mA)� The unit is then ready for operation�
In case of power failure or interruption all settings remain�

Operating indicators 

         

Green LED bar: current flow within the representa

-

tion range�

         

LED 9 flashes: current flow above the

representation range�

         

LED 0 flashes: current flow far below the represen

-

tation range�

Interference indicators

Display OFF

(no LED lights):

Operating voltage too low (< 19 V) or failed�

Ensure a correct voltage supply�

Содержание SI0551

Страница 1: ...Operating instructions Flow monitors SI0551 SI5004 704339 02 04 2021 UK...

Страница 2: ...s of interference in the pipe system 6 3 3 Mounting operation 6 4 Electrical connection 7 5 Operating and display elements 7 6 Set up and settings for water 8 6 1 High flow adjustment optional 8 7 Add...

Страница 3: ...roper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit...

Страница 4: ...the characteristic curve of the sensor Like the row of LEDs it indicates the relative flow velocity within the detection range set In case of excess flow flow velocity exceeds the detection range the...

Страница 5: ...ation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Страница 6: ...ces of interference 3 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads...

Страница 7: ...t be adhered to Voltage supply to EN 50178 SELV PELV Disconnect power Connect the unit as follows Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue n c not connected 5 Operating and display...

Страница 8: ...ay Carry out high flow adjustment 6 1 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 1 You can restore the factory setting any time 7...

Страница 9: ...flashes Release the pushbutton The unit adopts the new value and passes into the operating mode 7 2 Restore the factory setting reset Press the pushbutton for at least 15 s LED 9 lights after approx 5...

Страница 10: ...ment was not adhered to Carry out the two adjustment operations again in the right sequence 9 Operation After every power on all LEDs light and go out again step by step during this time the output si...

Страница 11: ...ce Recommended maintenance Check the sensor tip for build up from time to time Clean it using a soft cloth Stubborn build up e g lime can be removed using a common vinegar cleaning agent More informat...

Страница 12: ...12...

Страница 13: ...13 UK...

Отзывы: