36
10.1 Parameter setting in general
1� Change from the RUN mode to the main menu
[
●
]
2� Select the requested parameter
[
▲
] or [
▼
]
3� Change to the setting mode
[
●
]
4� Change the parameter value
[
▲
] or [
▼
] > 1 s
5� Acknowledge the set parameter value
[
●
]
6� Return to the RUN mode
> 30 seconds (timeout)
If [
🔒
Locked via Communication] is displayed when an attempt is made to
modify a parameter value, an IO-Link communication is active (temporary
locking)�
If [
🔒
Locked via system] is displayed, the sensor is permanently locked
via software� This locking can only be removed with a parameter setting
software�
10.1.1 Select submenu
1� Press [
●
] to change from the process value display to the main menu�
2�
Press [▼] to select the menu EF and press [●
]�
3�
Press [▼] to select the submenu and press [●
]�
10.1.2 Change to the process value display (RUN mode)
There are 2 possibilities:
1� Wait for 30 seconds
2�
Press [▲] or [▼] to go to the end of the menu and change to the next higher
menu�
10.1.3 Lock / unlock
The unit can be locked electronically to prevent unintentional settings� On delivery:
not locked�
Locking:
►
Make sure that the unit is in the normal operating mode�
► Press [▲] and [▼] simultaneously for 10 s until [
🔒
Set Menu lock] is displayed�