28
Explanation submenu OUT2
Parameter
Explanation and setting options
SEL2
standard measured variable for evaluation by OUT2:
FLOW (volumetric flow) or TEMP (temperature) or PRES (pressure)
ou2
output function for OUT2:
•
flow Hno, Hnc, Fno, Fnc, I, ImP
•
temperature: Hno, Hnc, Fno, Fnc, I
•
pressure: Hno, Hnc, Fno, Fnc, I
Hno = switching signal with hysteresis function normally open
Hnc = switching signal with hysteresis function normally closed
Fno = switching signal with window function normally open
Fnc = switching signal with window function normally closed
ImP = consumed quantity monitoring (totaliser function)
I
= analogue signal 4���20 mA�
In.D
= input for external counter reset signal
OFF = output OFF (of high impedance)
ASP2
analogue start point for OUT2
AEP2
analogue end point for OUT2
SP2
set point for OUT2
rP2
reset point for OUT2
FH2
upper limit value for OUT2
FL2
lower limit for OUT2
ImPS2
pulse value = volumetric flow quantity at which 1 pulse is provided�
ImPR2
configuration of OUT2 for consumed quantity monitoring: YES (pulse
signal), no (switching signal)�
DIn2
reset of the totaliser via external signal: +EDG, -EDG, HIGH, LOW
dS2
switching delay on OUT2
dr2
switch-off delay on OUT2
FOU2
response of OUT2 in case of an internal fault:
OU = output reacts as in normal case
On = output switches ON / analogue signal goes to 21�5 mA�
OFF = output switches OFF / analogue signal goes to 3�5 mA�
FOU2 is not available if ou2 = ImP was selected�