18
> Return to the next higher menu level� The changed parameter settings are not
accepted�
9.1.3 Change to the process value display (RUN mode)
There are 3 possibilities:
1� Wait for 30 seconds
�
2� Change from the submenu to the main menu, from the main menu to the pro-
cess value display with [▲] or [▼].
3� Press [
▲
] + [
▼
] simultaneously until the RUN mode is reached�
9.1.4 Locking / Unlocking
The unit can be locked electronically to prevent unintentional settings� On delivery:
not locked�
Locking:
►
Make sure that the unit is in the normal operating mode�
► Press [▲] and [▼] simultaneously for 10 s until [Loc] is displayed.
During operation: [LOC] is briefly displayed if you try to change parameter
values�
Unlocking:
►
Make sure that the unit is in the normal operating mode�
► Press [▲] and [▼] simultaneously for 10 s until [uLoc] is displayed.
9.1.5 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged values�
9.2 Settings for consumed quantity monitoring
9.2.1 Limit value monitoring with OUT1 / hysteresis function
►
Select [SEL1] and set [FLOW]�
►
Select [ou1] and set the switching function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
►
Select [SP1] and set the value at which the output is set�
►
Select [rP1] and set the value at which the output is reset�
Menu CFG:
[SEL1]
[ou1]
Main menu:
[SP1]
[rP1]