Mechatronic flow sensor
SBx4xx
7
5 Mounting
CAUTION
During installation or in case of a fault (e.g. housing damage) media under high pressure or
hot media can leak from the system.
w
Risk of injury caused by pressure or burns.
u
Ensure that the system is free of pressure during installation.
u
Ensure that no media can leak at the mounting location during installation.
u
Equip the unit with suitable protection (e.g. cover) to avoid hazard to personnel from
leaking media.
5.1 Process connection
u
Avoid major changes of cross section on the inlet side.
u
Fit the unit in the pipe in accordance with the flow direction (arrow) and tighten at the spanner flats.
Do not clamp the housing in a vice.
IN
OUT
1
Fig. 2: Process connection
IN:
Inlet
OUT:
Outlet
Loosening the socket head screw (1) and moving the cap do not change the setting of the
sensor. However, moving the cap may be useful to read the label.
Calming sections on the sensor's inlet or outlet side are not necessary.
The sensor can also prevent backflow.
5.2 Interference
u
The following minimum distances must be adhered to:
Distance between the sensor and ferromagnetic materials
≥ 30 mm *
Distance between the sensor and constant / alternating fields
≥ 500 mm
Distance between the sensor axes for side-by-side installation
≥ 50 mm
* The pipe may consist of ferromagnetic material.
GB