6
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (
Ò
Functions and features).
• Only use the product for permissible media (
Ò
Technical data).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator.
• Protect units and cables against damage.
3 Getting started
The unit has two configurable outputs for flow and temperature monitoring.
The process values and error messages can be read from the display.
All process values and messages are available via the IO-Link interface
irrespective of the output configuration.
3.1 Device function with factory setting
Factory setting
Operating mode
• Relative flow measurement in % of the maximum flow
Output OUT1
• Switching signal for flow:
– hysteresis function normally open, PnP
– SP1 = 20 %, rP1 = 15 % of the final value of the measuring
range
• Measured value damping 0.6 seconds
• No switch-on /switch-off delay
• In case of a fault the output switches OFF
Output OUT2
• Analogue signal for flow (4…20 mA; measuring range
unscaled)
• In case of a fault the analogue signal goes to 3.5 mA