17
UK
9 Parameter setting
During parameter setting the unit remains in the operating mode� It continues its
monitoring function with the existing parameters until the parameter setting has
been completed�
9.1 General parameter setting
3 steps must be taken for each parameter setting:
1
Parameter selection
►
Press [Mode/Enter] until the
requested parameter is displayed�
2
Setting of the parameter value
►
Press [Set] and keep it pressed�
> Current setting value of the
parameter flashes for 5 s�
> After 5 s: setting value is changed:
incrementally by pressing the button
once or continuously by keeping the
button pressed�
Numerical values are incremented continuously� To reduce the value: let the display
move to the maximum setting value� Then the cycle starts again at the minimum
setting value�
3
Acknowledgement of the parameter
value
►
Press [Mode/Enter] briefly�
> The parameter is displayed again�
The new setting value is stored�
Setting of other parameters:
►
Start again with step 1�
Finishing the parameter setting:
►
Press [Mode/Enter] several times until the current measured value is displayed or wait
for 15 s�
> The unit returns to the operating mode�