29
UK
Display
Status LED
OUT1
Status LED
OUT2
Type of fault *
)
Fault / warning
Corrective measures
UL
W Process value too low
(value below measuring
range)�
►
Check / increase system
pressure / select unit with
corresponding measuring
range�
Err
flashes
F Internal fault / malfunction�
►
Contact the manufacturer�
*
)
F = fault
W = warning
**
)
The output remains deactivated as long as the excessive current / short circuit
continues�
11 Technical data
11.1 Setting ranges
The setting ranges depend on the operating mode
11.1.1 Setting ranges in operating mode 2
rP / SP
cFL / cFH
ΔP
Setting range Min� distance Setting range Min� distance
PN7160
PN7560
bar
2���600
2
0���600
2
2
psi
20���8700
40
0���8700
40
20
MPa
0�2���60
0�2
0���60
0�2
0�2
PN7070
PN7570
bar
2���400
2
0���400
2
2
psi
20���5800
40
0���5800
40
20
MPa
0�2���40
0�2
0���40
0�2
0�2
PN7071
PN7571
bar
1���250
2
0���250
2
1
psi
20���3620
20
0���3620
20
20
MPa
0�1���25
0�2
0���25
0�2
0�1
ΔP = step increment