9.3.3 Zero-point calibration
►
Select [COF] and set a value between -5% and 5% of the final value of
the measuring range� The internal measured value "0" is shifted by this
value�
Zero-point calibration reset:
►
Press [Mode/Enter] until [CAr] is displayed�
►
Press and hold [Set] until [---] is displayed�
►
Briefly press [Mode/Enter]�
9.3.4 Set delay time for OUT1
[dS1] = switch-on delay for OUT1�
[dr1] = switch-off delay for OUT1�
►
Select [dS1] or [dr1] and set a value between 0�1 and 50 s (at 0�0 the
delay time is not active)�
9.3.5 Setting the damping for OUT1
►
Select [dAP] and set a value between 0�01 and 4�00 s; (at 0�00 [dAP] is
not active)�
dAP value = response time between pressure change and change of the
switching status in seconds�
[dAP] influences the switching frequency: f
max
= 1 ÷ 2dAP�
9.4 Service functions
9.4.1 Read min/max values for the system pressure
►
Select [HI] or [LO], briefly press [Set]�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press and hold [Set] until [---] is displayed�
►
Briefly press [Mode/Enter]�