14
9.2 Set output signals
9.2.1 Set switching limits
►
Select [SP1] and set the value at which the output switches�
►
Select [rP1] and set the value at which the output switches off�
rP1 is always lower than SP1� The unit only accepts values which are lower
than SP1�
9.2.2 Setting of the output function
►
Select [ou1]
[Hno] = hysteresis function/normally open,
[Hnc] = hysteresis function/normally closed,
[Fno] = window function/normally open,
[Fnc] = window function / normally closed�
9.3 User settings (optional)
9.3.1 Set the unit of measurement for system pressure
►
Select [Uni] and set the unit of measurement: [bAr] (= bar / mbar), [PA]
(= MPa / kPa), [inH] (= inHg), or [PSI]�
For units with a measuring range of > 999 PSI, 1/10 of the PSI value is
displayed� Consequently, the display value is to be multiplied by the factor
10�
Example: Display value = 15; real value = 15 * 10 = 150 PSI�
The unit is delivered with stickers for different units of measurement and
correction factors� Attach the corresponding sticker to the unit or mark the
sticker�
9.3.2 Configuration of the display
►
Select [diS] and set the update rate and orientation of the display:
[d1]: update of the measured values every 50 ms�
[d2]: update of the measured values every 200 ms�
[d3]: update of the measured values every 600 ms�
[Ph]: display of the pressure peaks remains for a short time (peak hold)�
[rd1], [rd2], [rd3], [Ph]: display as for d1, d2, d3, Ph; rotated by 180°�
[OFF]: the display is switched off in the operating mode�