22
7.4.4 List of the parameters
Parameter Function
ASP2
Analogue start point
Measured value at which 4 mA is provided�
AEP2
Analogue end point
Measured value at which 20 mA is provided�
Minimum distance between ASP and AEP = 20 % of the measuring span
uni
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [mWS] / [inH2O]
The selectable units of measurement depend on the respective unit�
coF
Zero-point calibration (calibration offset)
Compared to the real measured value, the internal measured value
(operating value of the sensor) is shifted�
• Teach range: - 3���+ 3 % of the measuring span
dAA
Damping for the analogue output
Pressure peaks of short duration or high frequency can be filtered out using
this function�
dAP
Damping of the process value (only applies to IO-Link evaluation)
Lo
Minimum value memory for system pressure (irrespective of the set
damping)
Hi
Maximum value memory for system pressure (irrespective of the set
damping)
7.5 Diagnostic functions
7.5.1 Read min/max values for the system pressure
►
Select [Hi] or [Lo] to display the highest or lowest measured process
value:
-[Hi] = Maximum value system pressure
-[Lo] = Minimum value system pressure
The memory can be reset�
[Hi]
[Lo]