PM11
Electronic pressure sensor
16
7.7 List of the parameters
Parameter
Function
ASP2
Analogue start point: Measured value at which 4 mA is provided.
AEP2
Analogue end point: Measured value at which 20 mA is provided.
Minimum distance between ASP and AEP = 20% of the measuring span.
uni
Standard unit of measurement for system pressure (display):
[bar] / [mbar] / [MPA] / [kPA] / [PSI] / [mWS] / [inH2O]
The selectable units of measurement depend on the respective device.
coF
Zero-point calibration (calibration offset). Compared to the real measured value, the internal meas-
ured value (operating value of the sensor) is shifted.
Setting range: -3%...+3% of the measuring span.
dAA
Damping for the analogue output. Pressure peaks of short duration or high frequency can be filtered
out using this function.
dAP
Damping of the process value (only applies to IO-Link evaluation).
Lo
Minimum value memory for system pressure (irrespective of the set damping).
Hi
Maximum value memory for system pressure (irrespective of the set damping).
7.8 Diagnostic functions
7.8.1 Read min/max values for the system pressure
u
Select [Hi] or [Lo] to display the highest or lowest measured process value:
[Hi] = maximum system pressure
[Lo] = minimum system pressure
[Hi]
[Lo]
The memory can be reset.