OMH551 OMH553 OMH555
Photoelectric distance sensor
16
The two system commands reset the device in a different way.
[Reset application]: The parameters of the technology-specific application are set to default
values. The identification parameters remain unchanged. An upload to the data memory of the
master is carried out, if activated in the port configuration of the master.
[Back-to-box]: The parameters of the device are set to the factory settings and communication
is blocked until the next time the device is switched off and on. Note: Disconnect the device
directly from the master port!
9.7 Additional parameter settings via IO-Link
9.7.1 Switch-on delay
A switch-on delay can be set for both switching outputs (0...10s).
u
Call up [Parameters] > [SSC1.1 / SSC1.2].
u
Select [SSC1.1 / SSC1.2 Switch-on delay].
u
Enter a switch-on delay between 0...10s.
To set a switch-on delay for [SSC1.2], this output must first be activated.
9.7.2 Switch-off delay
A switch-off delay can be set for both switching outputs (0...10s).
u
Call up [Parameters] > [SSC1.1 / SSC1.2].
u
Select [SSC1.1 / SSC1.2 Switch-off delay].
u
Enter a switch-off delay between 0...10s.
To set a switch-off delay for [SSC1.2], this output must first be activated.
9.7.3 Filter
Setting the filter property in relation to the detection speed.
4 options can be selected.
•
[HIGH] (Slow detection, precision)
•
[MEdi] (Standard)
•
[LOW] (Average detection, filtering of individual interference pulses)
•
[OFF] (Fast detection, without filtering)
u
Call up [Parameters] > [Signal].
u
Select [FILT].
u
Set one of the options.
9.7.4 Transmitter configuration
Setting to activate and deactivate the transmitter.
4 options can be selected.
•
[OFF / Off] (permanently off)
•
[ON / On] (permanently on)