OGD25x OGD55x
Photoelectric distance sensor
32
u
Confirm by clicking on [●].
w
The setting is confirmed.
11.3.2.2 Parameter setting via IO-Link
u
Call up [Parameter] > [Digital Output 1 / Digital Output 2].
u
Select [dS1 / dS2] for a switch-on delay and [dr1 / dr2] for a switch-off delay.
u
Set a delay time between 0...5 s.
11.3.3 Setting a fault suppression time
A fault suppression time can be set for both outputs.
Setting range [s]: 0...5 s in steps of 0.01 s
(0 = fault suppression time is not active)
The sensor faults [++], [--] and [ERP] are suppressed.
The set fault suppression time applies to [OU1] and [OU2].
11.3.3.1 Parameter setting via the device keys
u
Change to [EF].
u
Use [▲/▼] to select the parameter [dFo].
u
Confirm by clicking on [●].
w
Set parameter value is displayed.
u
Keep [▲] or [▼] pressed for at least 3 s.
u
Set the parameter value using [▲/▼].
u
Confirm by clicking on [●].
w
The setting is confirmed.
11.3.3.2 Parameter setting via IO-Link
u
Call up [Parameter] > [Output configuration].
u
Select [dFo].
u
Set a fault suppression time between 0...5 s.
11.3.4 Output logic (PNP/NPN)
It is possible to set the output logic in the device.
•
[PnP]: PNP positive switching
•
[nPn]: NPN negative switching
11.3.4.1 Parameter setting via the device keys
u
Change to [EF].
u
Use [▲/▼] to select the parameter [P-n].
u
Confirm by clicking on [●].
w
Set parameter value is displayed.