O1D111
Photoelectric distance sensor
12
Parameter
Explanation
[OU2]
Configuration for output 2
4 switching functions and 2 analogue signals can be selected:
[Hno], [Hnc], [Fno], [Fnc], [I], [U]
[SP2]
Switch point for hysteresis function OUT2
Limit value at which the output with selected hysteresis function changes its switching state (object near-
er/farther than distance set).
[SP2] is only active if [OU2] = [Hno] or [Hnc].
Setting of the switch point for hysteresis function OUT2 (
[nSP2]
[FSP2]
Switch points for window function OUT2
Values at which the output with selected window function changes its switching state (object present /
not present between the distance "near" and the distance "far").
[nSP2] = switch point "near" / [FSP2] = switch point "far".
[nSP2] / [FSP2] are only active if [OU2] = [Fno] or [Fnc].
Setting of the switch points for window function OUT2 (
[ASP]
Analogue start point
Measured value at which 4 mA / 0 V are provided.
[ASP] is only active if [OU2] = [I] or [U].
Scaling of the measuring range (analogue output) (
[AEP]
Analogue end point
Measured value at which 20 mA / 10 V are provided.
[AEP] is only active if [OU2] = [I] or [U].
Scaling of the measuring range (analogue output) (
[TEAC]
Teach mode
Selection "sampling rate" or "repeatability"
[EF]
Extended functions
Press [SET] to open the submenu "Extended functions".
[dS1]
[dr1]
[dS2]
[dr2]
Delay for the switching outputs
[dSx] = switch-on delay; [drx] = switch-off delay.
The output does not immediately change its switching state when the switching condition is met but only
after the delay has elapsed. If the switching condition is no longer met after the delay has elapsed, the
switching state of the output does not change.
[dS2] and [dr2] are not effective if [OU2] = [I] or [U].
Set the delay time for switching outputs (
[dFo]
Setting of the fault suppression time for switching outputs/analogue output
This function suppresses brief saturation of the measuring element (such saturation may result from di-
rect reflection or strong fluctuations in brightness). During the set delay time, the latest valid value meas-
ured is displayed, the output signals remain unchanged. Setting of the fault suppression time for switch-
ing output / analogue output (
[diS]
Setting of the display
7 settings can be selected:
[d1], [d2], [d3], [rd1], [rd2], [rd3], [OFF]
[Uni]
Setting of the display unit
Select the unit of measurement for [SP1], [SP2], [ASP], [AEP]
Options: [ [mm], [m]
Selection of the display unit (
[rES]
Restore factory settings
Reset all parameters to factory setting (
[SW]
Display of the software version number