19
UK
Wall thickness [mm]
1���5
5���8
8���11
Bore hole diameter [mm]
35
45
55
►
Install the flange plate with the flat surface showing to the tank and fix it with
appropriate screws�
A seal (B in fig� 6-11) can be inserted between flange plate and tank� Some
flange plates are supplied with a seal�
►
Ensure cleanness and evenness of the sealing areas, especially if the tank is
under pressure� Tighten the fixing screws sufficiently�
►
Screw the unit into the flange plate using the process connection and tighten
firmly�
►
Make sure that the supplied sensor seal (A in fig� 6-11) is correctly positioned�
6.4.3 Installation in open tanks
►
For installation in open tanks, use a metal fixture to install the unit� It serves
as a launching plate (R); Minimum size: 150 x 150 mm for a square fixture,
150 mm diameter for a circular fixture�
►
If possible, mount the unit in the middle of the fixture� The distance D2 must
not be below 40 mm, higher for probe lengths > 700 mm and in case of heavy
soiling (→ 6.1.1):
D2
150 mm
R
►
The lower edge of the process connection should be flush with the installation
environment (see fig� 6-7)�
►
Avoid non-flush installation (see fig� 6-8)�
►
Use seals or washers (see D in fig� 6-9) to reach the required height�