10.4 Define overflow switch point (OP)
Output OUT-OP is fixed to NC and has a fixed hysteresis of 10 mm�
►
Select [OP] and a value at which output OUT-OP switches�
OP
10.5 Set the output signals of the outputs OUT1...OUT3
10.5.1 Setting of the output function
Output OUT-OP (overflow prevention) is fixed to NC [Hnc] for safety
reasons� The principle of normally closed operation ensures that wire
break or cable break is also detected�
►
Select [OU1] ��� [OU3] and set the switching function:
[Hno] = hysteresis function/normally open
[Hnc] = hysteresis function/normally closed
[Fno] = window function/normally open
[Fnc] = window function/normally closed
OU1
...
OU3
10.5.2 Set the switching limits (hysteresis function)
►
Make sure that the function [Hno] or [Hnc] is set for [OUx]�
►
Select [SP1] ��� [SP3] and set the value at which the output switches�
SP1
...
SP3
►
Select [rP1] ��� [rP3] and set the value at which the output switches off�
rPx is always smaller than SPx� The unit only accepts values which are
lower than the value for SPx�
rP1
...
rP3
10.5.3 Set the switching limits (window function)
►
Make sure that the function [Fno] or [Fnc] is set for [OUx]�
►
Select [FH1] ��� [FH3] and set the upper limit of the acceptable range�
FH1
...
FH3
►
Select [FL1] ��� [FL3] and set the lower limit of the acceptable range�
FLx is always lower than FHx� The unit only accepts values which are lower
than the value for FHx�
FL1
...
FL3